background image

 

TCI-W13-U, TCI-W23-U Universal Controller 

I

NPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 11-22 

Subject to alteration 

Control configuration (Password 241) 

Input configuration 

Internal inputs 1T temperature and 1H humidity (with added AES3-HT-A2, -A3 or -A5 element) 

Parameter 

Description 

Range 

Default 

1T 00 

1H 00  Enable internal sensor 

OFF/ON 

ON 

1T 01 

1H 01  Display minimum value 

-50

205 

1T 02 

1H 02  Display maximum value 

-50

205 

100 

1T 03 

1H 03  Sensor sampling rate (control speed decrease as rate increases) 

0

100 

10 

1T 04 

1H 04  Sensor calibration 

per input 

1T 05 

1H 05  Alarm 1 (1T), Alarm 3 (1H) low limit 

OFF/ON 

OFF 

1T 06 

1H 06  Alarm 1 ((1T), Alarm 3 (1H) low limit values 

-40

215°C 

5°C/5% 

1T 07 

1H 07  Alarm 2 (1T), Alarm 4 (1H) high limit 

OFF/ON 

OFF 

1T 08 

1H 08  Alarm 2 (1T), Alarm 4 (1H) high limit values 

-40

215°C 

50°C / 95% 

1T 09 

1H 09  Hysteresis Alarm 1, 2 (1T), 3, 4 (1H) 

0

100° 

5°C/5% 

1T 10 

1H 10  Calculate a range of inputs (0= not active):  

1= average,  2= minimum,  3= maximum,  4= differential 

0

Universal inputs 1U = UI1, external passive input 2T = TI2 (TCI-W23-U only) 

1U 00  2T 00  Signal type (0= not active): 

1= 0-10V or 0-20mA,  2= 2-10V or 4-20mA,  3= passive temperature 

0

1U 01  2T 01  Display minimum value 

-50

205 

1U 02  2T 02  Display maximum value 

-50

205 

100 

1U 03  2T 03  Analog input display range: 0= x 0.1,  1= x 1,  2= x 10,  3 = x 100 

0

1U 04  2T 04  Analog input unit of measure:  0= no unit,  1= %,  2= °C /°F,  3= Pa 

0

1U 05  2T 05  Sensor sampling rate (control speed decrease as rate increases) 

0

100 

10 

1U 06  2T 06  Sensor calibration  

Per input

 

1U 07  2T 07  Alarm 5 (1U), Alarm 7 (2T) low limit 

OFF/ON 

OFF 

1U 08  2T 08  Alarm 5 (1U), Alarm 7 (2T) low limit value 

-40

215°C 

5°C(41°F) 

1U 09  2T 09  Alarm 6 (1U), Alarm 8 (2T) high limit 

OFF/ON 

OFF 

1U 10  2T 10  Alarm 6 (1U), Alarm 8 (2T) high limit value 

-40

215°C 

50°C(122°F) 

1U 11  2T 11  Hysteresis alarm 5 and 6 (1U), Alarm 7 and 8 (2T) 

0

100° 

5°C(10°F) 

1U 12  2T 12  Calculate a range of inputs (0=not active):  

1= average, 2= minimum, 3= maximum, 4= differential 

0

 

Set jumpers on the back of the controller: 0

10VDC (default), 0

20mA, or RT/DI (passive temperature or binary) 

 

Further define analog inputs with U00 

 

Match sensor range to input display. With a differential pressure transmitter having 0

200 Pa measuring range set 

UO1 display minimum to 0 and U02 display maximum to 200. The allowable range value of -50

205 may be adjusted 

with multipliers inU03. The largest displayable values are -990

9999. Limiting range increases resolution. Applies to 

analog as well as passive temperature inputs. 

 

For binary input (open/close contact) set the jumper to RT/DI and parameter U00 to an analog input.  An open 

contact reads as a high value (100%), a closed contact as a low value (0%).  

 

Enable / Disable an alarm. Setting the alarm enable to OFF will prevent the alarm from being displayed on screen. It 
may never the less be used to control an output by setting the appropriate output alarm flags. This way, an alarm 

limit may be used as interlock.  

 

Specify the input value that triggers an alarm. Hysteresis is the difference between alarm level input and value 

required to turn the alarm off. An alarm is displayed as text if enabled (see table). Alarm text can be set to blink 

continuously until acknowledged by pressing the OPTION button or only while the alarm conditions are active (see 

user parameter UP15).  

 

Calculate mathematical functions over multiple inputs for loop control or display with xU12. In order to calculate 

average, minimum or maximum between several inputs, make sure all the inputs are of identical type and range and 

then activate the same function on xU12 on all the selected inputs. The largest input of the group selected will carry 

the calculated value. For example: When average is activated on 2T12 and 1U12 = 1, the average is carried on UI2. 

UI2 may now be used as input for control loops and it will show the average value of UI1 and TI2 combined. It is 

possible to use different functions on different inputs. For example: minimum of UI1 and UI3 and maximum of UI2 

and UI4. 

 

The differential function may only be calculated on subsequent inputs. Such as TI2-UI1. The function must only be 

activated on the minuend (TI2 in this example). The displayed value of the minuend will change into the difference: 

TI2 in 

 UI1 = TI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the 

subtraction to UI1-TI2. 
 

Input 

1T 

1H 

1U 

2T 

Low limit 

ALA1 

ALA3 

ALA5 

ALA7 

High limit 

ALA2 

ALA4 

ALA6 

ALA8 

Summary of Contents for TCI-W13-U

Page 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Page 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Page 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Page 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Page 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Page 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Page 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Page 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Page 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Page 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Page 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Page 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Page 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Page 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Page 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Page 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Page 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Page 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Page 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Page 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Page 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Page 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...

Reviews: