TCI-W13-U, TCI-W23-U Universal Controller 

O

UTPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 16-22 

Subject to alteration 

Digital output configuration (1d) 

Settings for digital outputs (1d00 = OFF, 1d05 = 0), 1d = DO1 

Parameter  Description 

Range 

Default 

1d 00 

Enable digital/PWM output 

OFF= DO1 is a digital output 

ON = DO1 is a PWM output 

ON/OFF 

OFF 

1d 01 

Select control loop or special function (0= OFF) 

1= LP1, 2= LP2 

3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 

4= Manual positioning (on/off) 

5= State functions 

0

1d 02 

When 1d01 = 1, configure output: 

0= Stage 1 heating/reverse 

1= Stage 1 cooling/direct 

2= Stage 1 heating and cooling, reverse and direct 

3= Stage 2 heating/reverse 

4= Stage 2 cooling/direct 
5= Stage 2 heating and cooling, reverse and direct

 

If 1d01 = 4 Manual positioning or time schedule controlled 

0= Time schedule controlled only 

1= Manual positioning and time schedule controlled 

When 1d01 = 5, select state functions:  

0= ON if controller operation state is ON 

1= ON while demand on any output 

2= ON while controller in heating mode and operation state ON 

3= ON while controller in cooling mode and operation state ON 

0

1d 03 

Switch-off delay (time output active with no more demand) 

Delay is in seconds or minutes depending on d09 

0

255 

90sec 

1d 04 

Switch-on delay(time demand active before output on) 

In state mode 1d01=5 outputs disabled during switch-on delay 

Delay is in seconds or minutes depending on d09 

0

255 

5 sec 

1d 05 

Activate PWM, set cycle time, seconds (>0activates, 0 deactivates) 

0

1650s 

0s 

1d 06 

Choose alarm to set output to ON (output OFF on conflicting alarms) 

 

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1

ALA8 



 

1d 07 

Choose alarm to set output to OFF (output OFF on conflicting alarms) 

 

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1

ALA8 



 

1d 08 

Display fan symbol while active 

ON/OFF 

OFF 

1d 09 

Binary switching delays in minutes or seconds 

OFF = delays are in seconds, ON = delays are in minutes 

ON, OFF 

OFF 

 

 

Low and high limit alarms are defined with input parameters. With output parameters assign 

an alarm to an output and select output state. Each alarm

’s required output

 can be 

individually selected. Multiple alarms can be signed to one output. Should one alarm be 

simultaneously selected to activate and deactivate the output, the one to de-activate has 

precedence.  

 

With manual positioning (1d01=4) position the output directly (ON/OFF). 

 

With dehumidifying (1d01=3) the maximum value is taken of cooling and dehumidifying. When the humidity is too 

high, cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will 

activate to maintain comfort.  

 

State functions (1d01=5) activate the output based on certain conditions with or without a demand for heating or 

cooling, in either occupied (comfort) or unoccupied (standby) mode. In Energy Hold OFF mode (EHO) the output will 

be off.

 

 

 

 

Output Priority  

1. Alarm level low 
2. Alarm level high 
3. Operation mode OFF 
4. Control function 

Summary of Contents for TCI-W13-U

Page 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Page 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Page 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Page 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Page 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Page 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Page 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Page 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Page 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Page 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Page 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Page 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Page 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Page 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Page 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Page 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Page 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Page 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Page 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Page 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Page 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Page 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...