background image

 

TCT-MZ 

Configuration 

 

Doc: 70-00-0588 V1.0, 20180928 

© Vector Controls GmbH, Switzerland 

Page 6 

Subject to alteration 

www.vectorcontrols.com 

Configuration  

The TCT-MZ is preset to work for most applications. However, it can be fine-tuned for special requirements through a 

simple parameter setup routine. The parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware version and revision. It is therefore important to use 

a matching product version and parameter set. The Firmware version and revision version can be found when pressing 

simultaneously the 

 and 

 keys during several seconds. On the upper 7 segment display, the firmware version can be 

found, on the lower 7 segment display the current revision index (or “sub-version”).  

Access to parameters 

The parameters can be changed as follows: 

 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the firmware version in the 

upper large digits and the revision in the lower small digits. Pressing any key will show: CODE. 

2.

 

Select a password using UP or DOWN buttons. Select 009 in order to get access to the user parameters  

Press OPTION after selecting the correct password.  

3.

 

Once logged in, the parameter is displayed immediately 

4.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN and 

MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to adjust 

the value. 

5.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

6.

 

Press the POWER key again so as to leave the menu. The unit will return to normal operation if no key is pressed 

for more than 5 minutes. 

User Parameters (Password 009) 

Parameter  Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON, OFF 

ON 

UP 01 

Enable access to set points 

ON, OFF 

ON 

UP 02 

Enable access to clock settings and time schedules 

ON, OFF 

ON 

UP 03 

State after power failure:  
0 = off, 1 = on, 2 = state before power failure 

0, 1, 2 

UP 04 

Reset time for party mode 

0…255 min 

10 min 

UP 05 

Reset time for manual override mode during time schedules 

0…255 min 

60 min 

UP 06 

Step or percentage control for ventilation setpoint:  

OFF: Step control (# Steps defined in UP07) 
ON: Percent (0…100% in 0.5% steps) 

ON, OFF 

OFF 

UP 07 

Number of steps if UP06 = OFF 

0…10 

UP 08 

Time format: OFF 24H, ON 12H (AM/PM) 

ON, OFF 

OFF 

 

 

Summary of Contents for TCT-MZ

Page 1: ...plications Control of ventilation systems for comfort and industrial applications General description The TCT MZ is a microprocessor controlled precision positioner with real time clock and time sched...

Page 2: ...0 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non...

Page 3: ...mmon U1 Analog output supply air 0 10 V DC U2 Analog output return air 0 10 V DC Mounting location On an easy accessible interior wall approx 1 5 m 4 5 above the floor in an area of average temperatur...

Page 4: ...are memorized and do not need to be reentered Depending on UP03 the unit will remain switched off switch on automatically or return to the operation mode it was in before the power failure Deluxe ver...

Page 5: ...schedules Press CLOCK key 2 sec Time schedule operation is enabled or disabled alternately Creating time schedules Step 1 Select a switching time Up to 8 Pr01 Pr08 Press CLOCK Key 2 sec SEL and curre...

Page 6: ...ct a password using UP or DOWN buttons Select 009 in order to get access to the user parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Page 7: ...OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 100 CP 12 Full supply mode Volume for return air OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 OFF Signal limitation for VAV systems The m...