background image

 

Humidistat TCY-BH

 

 

Doc: 70-00-0142, V1.4, 20160912 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

www.vectorcontrols.com 

TCY-BH Humidistat 

Features 

 

Control for binary humidifiers and dehumidifiers with 

or without fan support.  

 

Low power energy consumption: < 1W per unit 

 

Relays switching for outputs each up to 300W 

 

Cost saving option with Economy functionality and set 

point limitations 

 

External sensor input for setpoint setback based on 

outdoor temperature 

 

Password protected programmable user and control 

parameters 

o

 

Setpoint range limitation 

o

 

Access control for setpoints and mode 

change 

o

 

Access control for clock and time programs 

o

 

Select your display contents 

o

 

Selectable behavior after return from power 

failure 

 

Temperature display of external input in Celsius or 

Fahrenheit 

Deluxe Version: 

 

Clock and time schedule functions 

 

Blue backlight for LCD 

Applications 

 

Humidifiers:  

o

 

On / Off type humidifiers 

o

 

On / Off type humidifiers with single speed fan support 

 

Dehumidifiers:  

o

 

On / Off type dehumidifiers 

o

 

On / Off type dehumidifiers with single speed fan support 

 

Combination humidifiers and dehumidifiers without fan support 

General description 

The TCY-BH is a stand-alone electronic binary humidity stat. The TCY-BH features one internal humidity sensor, one 

external NTC temperature sensor input and two binary outputs (Relays).  
A detailed parameterization is possible with the use of a simple configuration routine. The TCY-BH can be configured 

using the standard operation terminal. No special tools or software is required.  

Ordering 

Item name 

Item code 

Variant 

Features 

TCY-BH 
TCY-BH-W04 

TCY-BH-W05 

40-10 0057 
40-10 0057-04 

40-10 0057-05 

standard 
humidifying 

de-humidifying 

Binary controller with 24VAC power supply:  
1 Internal humidity input 

1 external temperature input (For set point shift) 

1 DO (Relay) for humidifier or dehumidifier 

1 DO (Relay) for fan (optional) 

TCY-BH-D 

TCY-BH-D-W04 

TCY-BH-D-W05 

40-10 0058 

40-10 0058-04 

40-10 0058-05 

Deluxe 

humidifying 

de-humidifying 

TCY-BH-230 

TCY-BH-230-W04 

TCY-BH-230-W05 

40-10 0063 
40-10 0063-04 

40-10 0063-05 

standard 

humidifying 

de-humidifying 

Binary controller with 230VAC power supply:  
1 Internal humidity input 

1 external temperature input (For set point shift) 

1 DO (Relay) for humidifier or dehumidifier 

1 DO (Relay) for fan (optional) 

TCY-BH-D-230 

TCY-BH-D-230-W04 

TCY-BH-D-230-W05 

40-10 0064 
40-10 0064-04 

40-10 0064-05 

Deluxe 

humidifying 

de-humidifying 

Accessories

 

 

 

 

SOD-Tn10-1 

AES3-HT-A5 

40-20 0108 
40-50 0104 

 

Outdoor sensor 

Replacement sensor 5% accuracy 

Summary of Contents for TCY-BH

Page 1: ...tion The TCY BH is a stand alone electronic binary humidity stat The TCY BH features one internal humidity sensor one external NTC temperature sensor input and two binary outputs Relays A detailed par...

Page 2: ...witching type AC switching power DO1 DO2 Relays 2 1 2 A 250VAC max fan power 300W Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 C 50 C 32 F 122 F 95 R H no...

Page 3: ...umidify CP11 ON FAN CP10 2 If CP11 ON FAN Dehumidify N L Power In DO1 Relay 2A NTC 10k 1 2 G0 G 24VAC DC 5 6 Q23 Q24 N L 3 4 Q13 Q14 N L DO2 7 8 B1 M RT ext NTC10k TCY BH Power In DO1 Relay 2A NTC 10k...

Page 4: ...er capacitor The time does not need to be re entered after a power failure Error messages The TCY BH may display the following error condition Err1 Humidity sensor faulty The humidity sensor is damage...

Page 5: ...time schedule Pro1 Pro4 by using UP DOWN keys and pressing the ENTER key 1 Enable or disable the Pro1 time schedule Choose ON or OFF with the UP DOWN keys The following steps will only be accessible...

Page 6: ...key will show CODE 2 Select a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3...

Page 7: ...cles and thus the wear on associated equipment 0 100 3 CP 08 Delay OFF Minimum running time MM SS Prevents a too short running cycle for the control output by setting a minimum running time 00 00 to 9...

Page 8: ...point towards a defined TSET set point CP15 depending on the outdoor temperature Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback...