background image

 

Humidistat TCY-BH

 

 

Doc: 70-00-0142, V1.4, 20160912 

© Vector Controls GmbH, Switzerland 

Page 2 

Subject to alteration 

www.vectorcontrols.com 

Technical specification 

Important notice and safety advice 

This device is for use as operating controls. It is not a safety device! Where a device failure endangers human life 

and/or property, it is the responsibility of the client, installer and system designer to add additional safety devices to 

prevent a system failure caused by such a device failure. Ignoring specifications and local regulations may cause 

equipment damage and endangers life and property. Tampering with the device and misapplication will void warranty. 

Power supply 

Operating voltage TCY-BH 

TCY-BH-230 

24V AC/DC ± 10 %, 50…60 Hz 

210 – 250V AC 50/60 Hz 

 

Power consumption 

Max. 1W, 1.5 VA 

 

Electrical connection 

Terminal Connectors,  

wire 0.34…2.5 mm

2

 (AWG 24…12)

 

 

Deluxe type only: 

Power backup for real time clock 

 

Min 48h if charged for 24h 

Signal inputs 

Humidity input:  
Range 

Accuracy 

 

Hysteresis 

Element: Polymer-Based Capacity Sensor 
0…100 % r.H.  

10%...90% r.H. 

 5.0 % 

0…10% and 90…100% 

 7.0 % 

±1% r.H. 

 

Temperature input 

Range 

External NTC (Sxx-Tn10 sensor):  

-40…70°C (-40…158 °F) 

 

Accuracy 

-40…0 °C (-40…32 °F): 0.5 K 
0…50 °C (32…122 °F): 0.2 K 
50…70 °C (122…158 °F): 0.5 K 

Signal outputs 

Digital switching outputs 

Switching type 

AC switching power 

DO1…DO2 
Relays 

2(1.2) A, 250VAC (max fan power 300W) 

Environment 

Operation 

Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 
class 3 K5 

0°C …50°C (32°F…122°F) 

<95% R.H. non-condensing 

 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3 K3 and class 1 K3 

-25°C…70°C (-13°F…158°F) 

<95% R.H. non-condensing 

class 2M2 

Standards 

 

conform according to  

EMC Directive 2004/108/EU 

LV Directive 2006/95/EU 

 

EN 61 000-6-1/ EN 61 000-6-3 

 

Product standards 

Automatic electrical controls for 

household and similar use 

 

EN 60 730 –1 

 

Degree of protection 

IP30 to EN 60 529 

 

Safety class 

 

TCY-BH 

 

 

 

TCY-BH-230 

III (IEC 60536) 
II (IEC 60536) 

 

Overvoltage category 

TCY-BH 

 

 

 

TCY-BH-230 

II (EN 60730-1) 

III (EN 60 730-1) 

Housing 

Cover, back part 

Mounting plate 

Fire proof ABS plastic (UL94 class V-0) 

Galvanized Steel 

General 

Dimensions (H x W x D) 

Front part:  

Power case TCY-BH: 

Power case TCY-BH-230 

 

88 x 88 x 21 mm (3.5” x 3.5” x 0.8”)  

ø 58 x 32 mm (ø 2.3” x 1.3”) 

60 x 50 x 32mm (2.4 x 2.0 x 1.3 in)

 

 

Weight (including package) TCY-BH 
 

 

 

TCY-BH-230 

260g (9.2 oz) 
295g (10.4 oz) 

Selection of devices and sensors 

External temperature sensors: Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is 

SDB-Tn10-15 as Duct sensor and SOA-Tn10 as outdoor sensor.  
Binary auxiliary devices: E.g. humidifiers, de-humidifiers and fans.  Do not directly connect devices that exceed 

2(1.2)A. Observe startup current on inductive loads! 

Summary of Contents for TCY-BH

Page 1: ...tion The TCY BH is a stand alone electronic binary humidity stat The TCY BH features one internal humidity sensor one external NTC temperature sensor input and two binary outputs Relays A detailed par...

Page 2: ...witching type AC switching power DO1 DO2 Relays 2 1 2 A 250VAC max fan power 300W Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 C 50 C 32 F 122 F 95 R H no...

Page 3: ...umidify CP11 ON FAN CP10 2 If CP11 ON FAN Dehumidify N L Power In DO1 Relay 2A NTC 10k 1 2 G0 G 24VAC DC 5 6 Q23 Q24 N L 3 4 Q13 Q14 N L DO2 7 8 B1 M RT ext NTC10k TCY BH Power In DO1 Relay 2A NTC 10k...

Page 4: ...er capacitor The time does not need to be re entered after a power failure Error messages The TCY BH may display the following error condition Err1 Humidity sensor faulty The humidity sensor is damage...

Page 5: ...time schedule Pro1 Pro4 by using UP DOWN keys and pressing the ENTER key 1 Enable or disable the Pro1 time schedule Choose ON or OFF with the UP DOWN keys The following steps will only be accessible...

Page 6: ...key will show CODE 2 Select a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3...

Page 7: ...cles and thus the wear on associated equipment 0 100 3 CP 08 Delay OFF Minimum running time MM SS Prevents a too short running cycle for the control output by setting a minimum running time 00 00 to 9...

Page 8: ...point towards a defined TSET set point CP15 depending on the outdoor temperature Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback...