Configuration parameters 

The TCY-BH is preset to work for most applications. For special requirements it can be fine-tuned to work ideally with a 

simple parameter setup routine. The parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware version and revision. It is therefore important to 

use a matching product version and parameter set. The Firmware version and revision version can be found when 

pressing simultaneously the 

 and 

 keys during several seconds. On the upper 7 segment display, the firmware 

version can be found, on the lower 7 segment display the current revision index (or “sub-version”).  

Access to parameters 

The TCY-BH is an 

intelligent 

controller and can be adapted to fit perfectly into your application. The control operation is 

defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters are password protected. There are two levels of parameters: User operation parameters for access 

control settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert 

levels are different. Only control experts should be given the control parameter password.  
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the firmware version in 

the upper large digits and the revision in the lower small digits. Pressing any key will show: CODE. 

2.

 

Select a password using UP or DOWN buttons. Select 009 in order to get access to the user parameters, 241 

for controls parameters.  

Press OPTION after selecting the correct password.  

3.

 

Once logged in, the parameter is displayed immediately 

4.

 

Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN 

and MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to 

adjust the value. 

5.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

6.

 

Press the POWER key again so as to leave the menu. The unit will return to normal operation if no key is 
pressed for more than 5 minutes. 

User parameters (code 009) 

Parameter 

Description 

Setting Range 

Factory Setting 

UP 00 

Enable change of operation modes  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Enable access to Time programs 

ON, OFF 

ON (Enabled) 

UP 03 

State after power failure:  

0 = Switched OFF, 1 = Switched ON, 2 = state before 

power failure 

0, 1, 2 

UP 04 

Enable Economy functionality 

ON, OFF 

OFF (Disabled) 

UP 05 

Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for 

Celsius 

ON, OFF 

OFF (Celsius) 

UP 06 

Select contents of small digits in standard mode: 
00 = OFF 

01 = Set point 

02 = Humidity Sensor 

03 = External Temperature Sensor  

04 = Clock 

0…5 

04 Deluxe:  

show clock 

01 Standard:  

show set point 

UP 07 

New: Resolution 0.5% or 1% RH 
OFF  = Display resolution is 0.5% RH 
ON  = Display resolution is 1% RH 

ON, OFF 

OFF (0.5% RH) 

UP 08 

Deluxe only 

Clock display type:  

OFF = Show 24hour clock 

ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 09 

Deluxe only 

Reset timer for override mode: Only available for deluxe 

version 

= Reset of override mode is not active.  

1…255 = delay in minutes to return to scheduled 

operation if the device is activated while scheduled 

to be in OFF or ECO mode.  

0…255 

60 (Min) 

 

Summary of Contents for TCY-BH

Page 1: ...tion The TCY BH is a stand alone electronic binary humidity stat The TCY BH features one internal humidity sensor one external NTC temperature sensor input and two binary outputs Relays A detailed par...

Page 2: ...witching type AC switching power DO1 DO2 Relays 2 1 2 A 250VAC max fan power 300W Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 C 50 C 32 F 122 F 95 R H no...

Page 3: ...umidify CP11 ON FAN CP10 2 If CP11 ON FAN Dehumidify N L Power In DO1 Relay 2A NTC 10k 1 2 G0 G 24VAC DC 5 6 Q23 Q24 N L 3 4 Q13 Q14 N L DO2 7 8 B1 M RT ext NTC10k TCY BH Power In DO1 Relay 2A NTC 10k...

Page 4: ...er capacitor The time does not need to be re entered after a power failure Error messages The TCY BH may display the following error condition Err1 Humidity sensor faulty The humidity sensor is damage...

Page 5: ...time schedule Pro1 Pro4 by using UP DOWN keys and pressing the ENTER key 1 Enable or disable the Pro1 time schedule Choose ON or OFF with the UP DOWN keys The following steps will only be accessible...

Page 6: ...key will show CODE 2 Select a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3...

Page 7: ...cles and thus the wear on associated equipment 0 100 3 CP 08 Delay OFF Minimum running time MM SS Prevents a too short running cycle for the control output by setting a minimum running time 00 00 to 9...

Page 8: ...point towards a defined TSET set point CP15 depending on the outdoor temperature Temperature setback becomes active when the outside temperature drops below the activation limit of temperature setback...

Reviews: