TCY-MT-U Series PI-temperature controller 

 

Features 

 

Temperature PI control for HVAC systems.  

 

Up to 2 modulating outputs for DC 0–10V with 10mV resolution.  

 

1 internal temperature sensor and up to 2 external sensor inputs 

 

Multiple remote control functions on external input 

 

Password protected programmable user and control parameters 

 

Blue backlight 

Applications 

 

Various temperature control applications 

 

Stand-alone VAV control for pressure independent actuators 

 

Water-only systems: Radiator, floor heating or chilled ceilings 

 

Individual room control for offices, residential, hotel rooms, 

meeting rooms, etc.  

 

General description 

The TCY-MT-U is a stand-alone electronic temperature controller with 

one control loop. It may use up to 2 PI-sequences. The TCY-MT-U 

features one internal NTC temperature sensor, up to two external sensor 

inputs and up to two analog outputs. The configuration has been 

reduced to a minimum to allow for simple and off-the-shelve usage. For 

more advanced features and current inputs and outputs the TCI product 

range is recommended. The TCY-MT-U can be configured using the 
standard operation terminal. No special tool or software is required.  

Name  

 

Ordering 

Item Name 

Item code 

Control Type 

Key-data 

TCY-MT2-U-W01 

40-10 0044-01 

Cooling only 

Compact PI controller with: 
2 TI, 1 AO 

TCY-MT2-U-W02 

40-10 0044-02 

Heating only 

TCY-MT2-U 

40-10 0044 

2-Pipe system 

TCY-MT4-U 

40-10 0046 

4-Pipe system 

1 TI, 2 AO 

Accessories

 

 

 

 

S-Tn10-2 

SD-Tn10-12-2 

SD-Tn10-20-2 

SDB-Tn10-12 

SDB-Tn10-20 

SOA-Tn10 

40-20 0001 
40-20 0002 

40-20 0003 

40-20 0051 

40-20 0004 

40-20 0006 

Flying lead sensor with 2 m cable 

Flying lead duct sensor 12cm immersion depth, 2m cable 

Flying lead duct sensor 20cm immersion depth, 2m cable 

Duct sensor with housing, 12cm immersion depth 

Duct sensor with housing, 20cm immersion depth 

Outdoor sensor

 

Selection of actuators and sensors 

Temperature sensors:  

Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-Tn10-20 as Duct sensor, SRA-

Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.  

Modulating actuators:  

Choose actuators with an input signal type of 0–10V DC or 2–10V DC.  

Housing:  

U  = Vertical (2x4”) housing, Standard is square housing 

Function: 

2  = 2 = 2-Pipe, 4 = 4-Pipe

 

Input: 

T  = Temperature, H = Humidity 

Output:  

M  = Modulating, B = Binary 

Series: 

TCY

 

T  C  Y 

-  M 

-  U 

(   )  

Summary of Contents for TCY-MT-U

Page 1: ...res and current inputs and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Name Item code Control Type Key data TCY MT2 U W01 40 10 0044 01 Cooling only Compact PI controller with 2 TI 1 AO TCY MT2 U W02 40 10 0044 02 Heating only TCY MT2 U 40 10 0044 2 Pipe system TCY MT4 U...

Page 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 Standards conform according to EMC Standard 89 336 EEC EMEI Standard 73 23 EEC EN 61 000 6 1 EN 61 000 6 3 Product standards Automatic electrical controls for household and similar use...

Page 3: ... sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install th...

Page 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT U may display the following error condition Err1 The connection to the temperature sensor may be interrupted or the temperature sensor is damaged The output is switched off Verify parameter settings and wiring Left POWER Press 2 sec Toggle STANDBY COMFORT mode or switch from...

Page 5: ...r DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter may be modified now Use UP and DOWN ke...

Page 6: ... U W01 Cooling mode YC1 1 TCY MT2 U W02 Heating mode YH1 2 TCY MT2 U Heating and Cooling 2 pipe system 3 TCY MT4 U Heating and Cooling 4 pipe system TCY MT2 U 0 2 TCY MT4 U 0 3 TCY MT2 U W01 0 TCY MT2 U W02 1 TCY MT2 U 2 TCY MT4 U 3 Proportional control P band The proportional control function calculates the output based on the difference between set point and measured value The proportional band ...

Page 7: ...T4 U heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 U heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 U cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 U cooling output 0 100 100 CP 17 Maximum Output in Economy unoccupied Mode Reduces the load on the system when is the space is unoccupied 0 100 50 Limiting the output signal The output signal 0 10V may be limited The lowe...

Page 8: ...motion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal Connecting the binary input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP18 3 Key c...