TCY-MT-U 

Technical Specifications 

 

Doc: 70-00-0176 V1.2, 20160114 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

www.vectorcontrols.com 

Installation and safety advice 

Caution!

 This device is intended to be used for comfort applications. Where a device failure endangers human life and/or 

property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent or detect a 

system failure caused by such a device failure. Vector Controls or its affiliates cannot be held liable for any damage 

caused by such a failure. Failure to follow specifications and local regulations may endanger life, cause equipment damage 

and void warranty.  

Connection diagram 

 

Description

:  

G0 

Power supply:  

0V, -24VDC, internally connected to signal common 

Power supply:  

24VAC, +24VDC 

Signal common:  

Common 0 potential for analog inputs and analog outputs. 

X1

 

External temperature input: 

NTC 10kΩ @ 25°C (77°F) 

 

TCY-MT2-U: 

 

X2

 

Changeover input: 

NTC 10kΩ @ 25°C (77°F) 

U1

 

Analog output:  

0…10 V DC 

 

TCY-MT4-U: 

U1

 

Analog heating output:  

0…10 V DC 

U2

 

Analog cooling output:  

0…10 V DC 

 

Installation 

The unit consists of two parts: (a) The power case with attached mounting plate and (b) the front part.  

Mounting location 

 

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature. 

 

Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical 

equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 

the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 

screw too much. 

 

X

T INT 

0V (COM) 

24V AC/DC 

 

TCY-MT4-U 

G0 

G0 

Signal   

COM 

 

U1 

Heat 

OUT 

 


  M  

Signal  

COM 

 

X1 

X

T EXT

 

IN 

 

G0 

Signal   

COM 

 

U2 

Cool 
OUT 

 

X

T INT 

0V (COM) 

24V AC/DC 

 

TCY-MT2-U 

G0 

G0 

COM 

 

U1 

H/C 

OUT 

 

X

T CO

 

IN 

 

X2 

COM 

 

X1 

X

T EXT

 

IN 

 

COM 

 

Summary of Contents for TCY-MT-U

Page 1: ...res and current inputs and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Name Item code Control Type Key data TCY MT2 U W01 40 10 0044 01 Cooling only Compact PI controller with 2 TI 1 AO TCY MT2 U W02 40 10 0044 02 Heating only TCY MT2 U 40 10 0044 2 Pipe system TCY MT4 U...

Page 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 Standards conform according to EMC Standard 89 336 EEC EMEI Standard 73 23 EEC EN 61 000 6 1 EN 61 000 6 3 Product standards Automatic electrical controls for household and similar use...

Page 3: ... sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install th...

Page 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT U may display the following error condition Err1 The connection to the temperature sensor may be interrupted or the temperature sensor is damaged The output is switched off Verify parameter settings and wiring Left POWER Press 2 sec Toggle STANDBY COMFORT mode or switch from...

Page 5: ...r DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter may be modified now Use UP and DOWN ke...

Page 6: ... U W01 Cooling mode YC1 1 TCY MT2 U W02 Heating mode YH1 2 TCY MT2 U Heating and Cooling 2 pipe system 3 TCY MT4 U Heating and Cooling 4 pipe system TCY MT2 U 0 2 TCY MT4 U 0 3 TCY MT2 U W01 0 TCY MT2 U W02 1 TCY MT2 U 2 TCY MT4 U 3 Proportional control P band The proportional control function calculates the output based on the difference between set point and measured value The proportional band ...

Page 7: ...T4 U heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 U heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 U cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 U cooling output 0 100 100 CP 17 Maximum Output in Economy unoccupied Mode Reduces the load on the system when is the space is unoccupied 0 100 50 Limiting the output signal The output signal 0 10V may be limited The lowe...

Page 8: ...motion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal Connecting the binary input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP18 3 Key c...

Reviews: