TCY-MT-U 

Configuration 

 

Doc: 70-00-0176 V1.2, 20160114 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

www.vectorcontrols.com 

Input configuration 

Parameter  Description 

Range 

Default 

CP 18 

Configuration of remote input (X1) 

0 = Control Input  

1 = Comfort/Economy Mode switch 

2 = Comfort/OFF Mode switch 

3 = Keycard switch function 

4 = Output enable 

0…4 

CP 19 

Activation delay (minutes): 
The time the binary input needs to be open before Economy or 
OFF mode is activated. 

0…255 min 

CP 20 

Fixed set point for key card function in heating mode 

0–60°C (32..160°F) 

17°C (63°F) 

CP 21 

Fixed set point for key card function in cooling mode 

0–60°C (32..160°F) 

27°C (81°F) 

CP 22 

For TCY-MT2-U only: Enable Auto changeover 

ON, OFF 

OFF 

CP 23 

For TCY-MT2-U only: Auto changeover limit heating 

0–60°C (32..160°F) 

30°C (86°F) 

CP 24 

For TCY-MT2-U only: Auto changeover limit cooling 

0–60°C (32..160°F) 

15°C (59°F) 

 

Configuring the function of the external input X1 

The external input X1 may be configured for several functions: 

 

CP18 = 0 

External control input 

The control input is provided by the external input. The internal input 

will not be used.  

CP18 = 1 

Switching Economy and 

Comfort modes 

Economy (unoccupied) and Comfort (occupied) modes are controlled 

through an external contact by connecting X1 through a dry contact to 

signal common. This function may be used together with key card 

switches for hotels or motion detectors for offices.

 

CP18 = 2 

Switching Energy Hold 

OFF and Comfort 

modes 

Opening the external temperature input will force the unit into the OFF 

operation mode. The operation mode cannot be overridden by using the 

terminal. Connecting the binary input to GND returns control of the 

operation mode to the terminal. This function may be used as window 

contact to prevent loss of energy.  

CP18 = 3 

Key card function 

As with CP18 = 1, the key card function switches economy 

(unoccupied) and comfort (occupied) modes. Instead of using the set 

point shift, the set points in unoccupied mode are defined by parameter 

CP20 and CP21.  

CP18 = 4 

Output enable 

This may be used for a dew point sensor input. Output will switch off if 
contact opens. 

 

Configuring auto changeover input X2 (TCY-MT2-U only):  

The auto changeover function automatically changes heating and cooling mode based on supply media 

temperature or outdoor temperature. The difference between the two is in the values of the changeover limits 

CP23 and CP24. See table below for recommended settings. 

Heating and cooling may be as well changed by an open contact switched to signal ground. Note: all signal 

ground levels of involved controllers must be the same in case more than one controller is switched.  

 

Recommended settings for CP23 and CP24: 

Change over mode 

Relation CP23 to CP24 

Example CP23 

Example: CP24 

Supply media 

CP23 > CP24 

25°C (77F) 

18°C (64F) 

Outside temperature 

CP23 < CP24 

15°C (59F) 

25°C (77F) 

Dry contact: Heating if contact closed 

CP23 > CP24 

25°C (77F) 

15°C (59F) 

Dry contact: Cooling if contact closed 

CP23 < CP24 

15°C (59F) 

25°C (77F) 

 

Summary of Contents for TCY-MT-U

Page 1: ...res and current inputs and outputs the TCI product range is recommended The TCY MT U can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Name Item code Control Type Key data TCY MT2 U W01 40 10 0044 01 Cooling only Compact PI controller with 2 TI 1 AO TCY MT2 U W02 40 10 0044 02 Heating only TCY MT2 U 40 10 0044 2 Pipe system TCY MT4 U...

Page 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2MT2 Standards conform according to EMC Standard 89 336 EEC EMEI Standard 73 23 EEC EN 61 000 6 1 EN 61 000 6 3 Product standards Automatic electrical controls for household and similar use...

Page 3: ... sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to be connected to the terminals of the power case according to wiring diagram 2 Install th...

Page 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT U may display the following error condition Err1 The connection to the temperature sensor may be interrupted or the temperature sensor is damaged The output is switched off Verify parameter settings and wiring Left POWER Press 2 sec Toggle STANDBY COMFORT mode or switch from...

Page 5: ...r DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediately 4 Select the parameters with the UP DOWN keys Change a parameter by pressing the OPTION key The MIN and MAX symbols show up and indicate that the parameter may be modified now Use UP and DOWN ke...

Page 6: ... U W01 Cooling mode YC1 1 TCY MT2 U W02 Heating mode YH1 2 TCY MT2 U Heating and Cooling 2 pipe system 3 TCY MT4 U Heating and Cooling 4 pipe system TCY MT2 U 0 2 TCY MT4 U 0 3 TCY MT2 U W01 0 TCY MT2 U W02 1 TCY MT2 U 2 TCY MT4 U 3 Proportional control P band The proportional control function calculates the output based on the difference between set point and measured value The proportional band ...

Page 7: ...T4 U heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 U heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 U cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 U cooling output 0 100 100 CP 17 Maximum Output in Economy unoccupied Mode Reduces the load on the system when is the space is unoccupied 0 100 50 Limiting the output signal The output signal 0 10V may be limited The lowe...

Page 8: ...motion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal Connecting the binary input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP18 3 Key c...

Reviews: