TCY-MT
Configuration
Doc: 70-00-0058 V1.2, 20160322
© Vector Controls GmbH, Switzerland
Page 7
Subject to alteration
www.vectorcontrols.com
T [°C, F]
U [V, mA]
Heating
Cooling
10
0
50
0
Y
H1
, Y
R1
W
H
X
DZ
Y
C1,
Y
D1
W
C
Max heating: CP14
Min cooling: CP15
Max cooling: CP16
Min heating: CP13
Output configuration
Parameter Description
Range
Default
CP 12
Manual Override Mode:
Allows manual control of the analog outputs for using the
controller as positioner or during commissioning.
ON, OFF
OFF
CP 13
Min output for AO1 (TCY-MT4 = heating output)
0 – 100 %
0%
CP 14
Max output for AO1 (TCY-MT4 = heating output)
0 – 100 %
100%
CP 15
Min output for AO2 (TCY-MT4 = cooling output)
0 – 100 %
0%
CP 16
Max output for AO2 (TCY-MT4 = cooling output)
0 – 100 %
100%
CP 17
Maximum Output in Economy (unoccupied)Mode
Reduces the load on the system when is the space is
unoccupied.
0 – 100 %
50%
Limiting the output signal
The output signal (0–10V) may be
limited. The lower limit for example may
be changed to 20% for a 2–10V actuator.
Other reasons for changing the limits are
VAV systems. By changing the limits the
minimum and maximum flows may be
adjusted without the need to access the
VAV actuator. The output limits may
thus be set individually for heating and
cooling mode: