Clock operation  

The TCY-MZ2-D contains a quartz clock with battery back-up (not available in TCY-MZ2). Up to 8 switching events based 

on time and day of the week may be programmed. A switching event is defined by the time, day of the week and 

ventilation setpoint.  

A blinking clock indicates that the time has not been set or that the unit has been without power for longer than 48 hours. 

The time needs to be set to allow time schedules to operate. 

 

Clock setup 

Press RIGHT Key > 2 sec. SEL and current time displayed 
Press RIGHT < 2 sec. to change time, 

Minutes blink: UP/DOWN to change, OPTION to save minutes,  
Hours blink: UP/DOWN to change, OPTION to save hour,  

Press RIGHT to save time, 

DAY1 blinks: UP/DOWN to change, OPTION to save day 

SEL 
  00:00  
  DAY1 (Mon) 

 

Enable/disable time schedules 

Press RIGHT > 2 sec. SEL and current time displayed 
Press UP:  

SEL and PRO displayed, clock symbol blinks 

Press RIGHT:  

Time schedule status displayed OFF or ON: 

Press RIGHT 

OFF/ ON blinks, UP/DOWN to change, OPTION to save  

SEL 
  PRO 

  

 

Pro 
  OFF/ON 

   

Creating time schedules  

Step 1: Select a switching time (Up to 8, Pr01–Pr08) 

Press UP while PRO-ON displayed: 

Large digits display Pr01, small digits display 00:00 

Press RIGHT: 00:00 blinks 
Press UP/DOWN to select switching time from 00:00–23:45 
Press RIGHT to save switching time 

 

   

Pr01 
  08:00

 

 

Step 2: Select day(s) of week during which the switching event shall be executed  

While Pr01 is displayed and DAY1 is blinking: 

Press UP: Activate switching event for DAY1 (triangle appears on 1), 
Press DOWN:  
 

Deactivate switching event for DAY1 (triangle disappears) 

Press RIGHT to step to next day: 

Repeat for DAY2 – DAY7 

  

Pr01 

   DAY1 

 

 

1 2 3 4 5 6 7 

Step 3: Define setpoint 

Press UP/DOWN to adjust the setpoint to the desired level 
Press RIGHT button to complete. The switching event is now defined. 

  

Pr01 

   08:00

 

 

Default switching times 

These switching times are preprogrammed:  

Monday to Sunday (Day1 to Day7:  

PR01:   07:00  

50% 

PR02:   17:00  

100% 

PR03:   22:00  

25% 

 

 

Summary of Contents for TCY-MZ

Page 1: ...pplications Control of ventilation systems for comfort and industrial applications General description The TCY MZ is a microprocessor controlled precision positioner with real time clock and time sche...

Page 2: ...H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class...

Page 3: ...wall approx 1 5 m 4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight Installation 1 Connect the wires to be connected to the terminals of the power case according...

Page 4: ...alue Power Failure All the parameters and set points are memorized and do not need to be reentered Depending on UP03 the unit will remain switched off switch on automatically or return to the operatio...

Page 5: ...ec SEL and current time displayed Press UP SEL and PRO displayed clock symbol blinks Press RIGHT Time schedule status displayed OFF or ON Press RIGHT OFF ON blinks UP DOWN to change OPTION to save SEL...

Page 6: ...ect a password using UP or DOWN buttons Select 009 in order to get access to the user parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediate...

Page 7: ...OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 100 CP 12 Full supply mode Volume for return air OFF 0V energy hold off 0 100 0 10V or 2 10V OFF 0 100 OFF Signal limitation for VAV systems The...

Reviews: