Setup For ProtoNode
Record Identification Data
Each ProtoNode has a unique part number located on the side or the back of the unit. This number should be
recorded, as it may be required for technical support. The numbers are as follows:
FPC-N54
units have the following 3 ports: RS-485 + Et RS-485/RS-232.
Point Count Capacity
The total number of registers presented the device attached to the ProtoNode cannot exceed:
Configuring Device Configurations
•
The connected serial device MUST have the same baud rate, data bits, stop bits, and parity settings as the
ProtoNode
•
To set the ProtoNode’s COM settings, see “Select Field Protocol and Set Configuration Parameters” on
•
Table 3 specifies the device serial port settings required to communicate with the ProtoNode.
Table 1. ProtoNode Part Number
Model
Part Number
ProtoNode
FPC-N54-1759
Table 2. ProtoNode Total Registers
Part Number
Total Registers
330020-840
5000
Table 3. COM Settings
Port Setting
TLS-3XX/TLS4XX
Protocol
V-R Interface
Baud Rate
9600
Parity
Odd
Data Bits
7
Stop Bits
1