Appendix A
Interface To BACnet & Modbus Tables
A-5
Table A-12. Smart_Sensor Veeder-Root Interface to BACnet, Modbus and SNMP
Table A-13. PLLD Veeder-Root Interface to BACnet, Modbus and SNMP
Point Name
BACnet
Object Type
BACnet
Object ID
Modbus
Register
SNMP OID
Smart Sensor X Setup Data Warninq
BI
X001
10X01
1.3.6.1.4.1.6347.0.XX1.1.0
Smart Sensor X Communication Alarm
BI
X002
10X02
1.3.6.1.4.1.6347.0.XX1.2.0
Smart Sensor X Fault Alarm
BI
X003
10X03
1.3.6.1.4.1.6347.0.XX1.3.0
Smart Sensor X Fuel Warning
BI
X004
10X04
1.3.6.1.4.1.6347.0.XX1.4.0
Smart Sensor X Fuel Alarm
BI
X005
10X05
1.3.6.1.4.1.6347.0.XX1.5.0
Smart Sensor X Water Warning
BI
X006
10X06
1.3.6.1.4.1.6347.0.XX1.6.0
Smart Sensor X Water Alarm
BI
X007
10X07
1.3.6.1.4.1.6347.0.XX1.7.0
Smart Sensor X High Liquid Warning
BI
X008
10X08
1.3.6.1.4.1.6347.0.XX1.8.0
Smart Sensor X High Liquid Alarm
BI
X009
10X09
1.3.6.1.4.1.6347.0.XX1.9.0
Smart Sensor X Low Liquid Warning
BI
X010
10X10
1.3.6.1.4.1.6347.0.XX1.10.0
Smart Sensor X Low Liquid Alarm
BI
X011
10X11
1.3.6.1.4.1.6347.0.XX1.11.0
Smart Sensor X Temperature Warning
BI
X012
10X12
1.3.6.1.4.1.6347.0.XX1.12.0
Smart Sensor X Relay Active
BI
X013
10X13
1.3.6.1.4.1.6347.0.XX1.13.0
Smart Sensor X Install Alarm
BI
X014
10X14
1.3.6.1.4.1.6347.0.XX1.14.0
Smart Sensor X Fault Warning
BI
X015
10X15
1.3.6.1.4.1.6347.0.XX1.15.0
Smart Sensor X Vacuum Warning
BI
X016
10X16
1.3.6.1.4.1.6347.0.XX1.16.0
Smart Sensor X No Vacuum Warning
BI
X017
10X17
1.3.6.1.4.1.6347.0.XX1.17.0
Point Name
BACnet
Object Type
BACnet
Object ID
Modbus
Register
SNMP OID
PLLD X Setup Data Warninq
BI
X001
10X01
1.3.6.1.4.1.6347.0.XX1.1.0
PLLD X Gross Test Fail Alarm
BI
X002
10X02
1.3.6.1.4.1.6347.0.XX1.2.0
PLLD X Annual Test Fail Alarm
BI
X003
10X03
1.3.6.1.4.1.6347.0.XX1.3.0
PLLD X Periodic Test Needed Warning
BI
X004
10X04
1.3.6.1.4.1.6347.0.XX1.4.0
PLLD X Periodic Test Needed Alarm
BI
X005
10X05
1.3.6.1.4.1.6347.0.XX1.5.0
PLLD X Sensor Open Alarm
BI
X006
10X06
1.3.6.1.4.1.6347.0.XX1.6.0
PLLD X High Pressure Alarm
BI
X007
10X07
1.3.6.1.4.1.6347.0.XX1.7.0
PLLD X Shutdown Alarm
BI
X008
10X08
1.3.6.1.4.1.6347.0.XX1.8.0
PLLD X High Pressure Warning
BI
X009
10X09
1.3.6.1.4.1.6347.0.XX1.9.0
PLLD X Continuous Handle On Warning
BI
X010
10X10
1.3.6.1.4.1.6347.0.XX1.10.0
PLLD X Periodic Test Fail Alarm
BI
X011
10X11
1.3.6.1.4.1.6347.0.XX1.11.0
PLLD X Annual Test Needed Warning
BI
X012
10X12
1.3.6.1.4.1.6347.0.XX1.12.0
PLLD X Annual Test Needed Alarm
BI
X013
10X13
1.3.6.1.4.1.6347.0.XX1.13.0
PLLD X Low Pressure Alarm
BI
X014
10X14
1.3.6.1.4.1.6347.0.XX1.14.0
PLLD X Sensor Short Alarm
BI
X015
10X15
1.3.6.1.4.1.6347.0.XX1.15.0
PLLD X Continuous Handle On Alarm
BI
X016
10X16
1.3.6.1.4.1.6347.0.XX1.16.0
PLLD X Fuel Out Alarm
BI
X017
10X17
1.3.6.1.4.1.6347.0.XX1.17.0
PLLD X Line Equipment Alarm
BI
X018
10X18
1.3.6.1.4.1.6347.0.XX1.18.0
PLLD X Gross Test Needed Alarm
BI
X019
10X19
1.3.6.1.4.1.6347.0.XX1.19.0