Setup For QuickServer
BMS Network Settings: MAC Address Node-ID And Baud Rate
8
BACNET MS/TP OR MODBUS RTU: SETTING THE BAUD RATE FOR BMS NETWORK
DIP switches B0 – B3 can be used to set the field baud rate of the QuickServer to match the baud rate required
by the BMS for BACnet MS/TP (see Figure 4).
Figure 4. QuickServer B Bank DIP Switches
BMS baud rate dip switch selections are shown in Table 5.
.
*Factory default setting.
Table 5. BMS Baud Rate
Baud Rate
B0
B1
B2
B3
9600
On
On
On
Off
19200
Off
Off
Off
On
38400*
On
On
Off
On
57600
Off
Off
On
On
76800
On
Off
On
On
6
B0 - B3 DIP Switches
Bank DIP Switch Location
B0
B1
B2
B3
Off
On
When setting DIP switches,
ensure that power to the
board is OFF.
NOTICE