Mag Probe Installation
Installing a LPG-ISO Mag Probe
34
Figure 27. Rain Shield Installed Position
ENTERING CUSTOM FLOAT SIZE (IN-TANK SETUP - VER. 22 OR LATER)
At the console, select Setup Mode/In-Tank Setup/Float Size. Press Change to display “Float Size: Custom”
1
. For
the Media-Isolated probe’s stainless steel float you need to enter a Fuel Offset value of +1.000 and an Invalid Fuel
value of +0003.300. (Water Offset and Water Minimum values are ignored for this probe so no changes are
necessary). The probe is now installed and setup.
Installing a LPG-ISO Mag Probe
•
This product is to be installed and operated in the highly combustible environment of an LPG storage tank. It is
essential that you carefully read and follow the warnings and instructions in this manual to protect yourself and
others from serious injury, explosion, or electrical shock.
•
For safety reasons, we have taken particular care in the design of this product to limit the power in the wiring to
the fuel tanks and to keep that wiring physically separated from any other wiring. It is your responsibility to
maintain the effectiveness of these safety features by installing this product in accordance with the instructions
and warnings which follow. Your failure to do so could create danger to life and property.
•
Failure to install this product in accordance with its instructions and warnings will result in voiding of all
warranties connected with this product. This unit does not contain any user controls. Opening or tampering with
a magnetostrictive probe will void the warranty.
BEFORE YOU BEGIN
1.
Make sure that the tank is depressurized (drained) and free of liquid and combustible vapors.
2. Remove any sludge from the bottom of the tank. Sludge can interfere with the proper operation of the float.
1. This offset can be entered using a “Tilt” value of +0.94” and 2-inch float entry on earlier software versions.