Probe and Sensor Field Wiring
Sealing Field Connections
53
gloves, eye, and face protection. Use only in well ventilated areas. Wash thoroughly before eating, drinking, or
smoking.
4. Do NOT terminate shield or drain wire in the field junction box, ground shield and drain wires at console only.
5. Place the bag with the resin sealed wiring connections in the junction box. Replace and tighten the junction
box cover.
DIRECT BURIAL CABLE
When using direct burial cable for probe- or sensor-to-console wiring runs, the sealing materials and procedure are
completely different. Refer to the Direct Burial Cable Installation Manual 576013-858.
Figure 52. Epoxy Sealing Probe and Sensor Field Connections
consoles\epxy2w.eps
To console
Tie wrap
Wire nuts
From probe,
sensor, or
transducer
A
C
B
Make sure that
the ends of cable
sheathing are sub-
merged in sealant
Instructions:
NOTE: When temperature is below 50˚F (10˚C), keep
resin in a warm place prior to mixing (e.g., in an
inside pocket next to body).
1. Open epoxy sealant package, and remove resin pak.
2. Holding resin pak as shown in A, bend pak along long
length.
3. As shown in B, firmly squeeze the RED SIDE of the
resin, forcing it through the center seal and into
BLACK SIDE.
4. Mix thoroughly to a uniform color by squeezing
contents back and forth 25-30 times.
5. Squeeze mixed, warm resin into one end of bag and
cutoff other end.
6. Slowly insert wiring connections into sealing pack
until they fit snugly against the opposite end as
shown in C.
7. Twist open end of bag and use tie wrap to close it off
and position the tie wrapped end up until the resin
jells.