Press
Function
until the display reads:
To test individual tanks press
Step
,
Change
,
Enter
and
Step
. To test all tanks press
Step
twice
and the display reads:
To end the test manually press
Change
,
Enter
and
Step
; or to set a duration for the test press
Step
. Select the test accuracy, either 0.2 gal/hr (0.76 lph) or 0.1 gal/hr (0.38 lph). To change the
setting press
Change
and
Enter
. Press
Step
to continue. Enter the Test Duration in hours, press
Enter
and
Step
. The display reads:
Press
Enter
to start the test. For individual tanks press
Tank
to go to the next tank.
START IN-TANK LEAK TEST
PRESS <STEP> TO CONTINUE
TEST CONTROL: ALL TANKS
TIMED DURATION
START LEAK TEST TANKS
PRESS <ENTER>
• Do not start an in-tank leak test if there
has been a delivery to the tank to be
tested within the previous 8 hours. This
will result in an invalid test.
• A delivery to a tank being tested results
in an invalid test.
• Dispensing from a tank being tested will
cause a Sudden Loss Alarm.
To Start In-Tank Leak Testing