Page
18
B
Backup
E
Enter
C
Change
F
Function
M
Mode
P
S
Step
T
Tank/Sensor
KEY SYMBOLS:
Press
until the display shows:
To test individual tanks press
. To test all tanks press
the display will show
To end the test manually press
or to set a duration for the test press
.
Select the test accuracy, either 0.20 gal/hr or 0.10 gal/hr. To change the setting press
. Press
to continue.
Enter the Test Duration in hours, press
. The display will show
Press
to start the test. For individual tanks press
to go to the next tank.
Return to normal operating mode: press
until the date and time display appears.
F
START IN-TANK LEAK TEST
PRESS <STEP> TO CONTINUE
consoles\qh\44.eps
S
C
E
S
S
S
TEST CONTROL: ALL TANKS
TIMED DURATION
consoles\qh\45.eps
C
E
S
S
C
E
S
E
S
START LEAK TEST TANKS
PRESS <ENTER>
consoles\qh\46.eps
E
T
F
To Start An In-Tank Leak Test
☞
Do not start an in-tank leak test if there has been a
delivery to the tank to be tested within the previous
8 hours. This will result in an invalid test.
☞
A delivery to a tank being tested results in an invalid
test.
☞
Dispensing from a tank being tested will cause a
Sudden Loss Alarm.
Summary of Contents for TLS-300
Page 1: ...Manual 576013 939 Rev D TLS 300 TLS 350 TLS 350R Operator s Quick Help...
Page 35: ......
Page 36: ...Manual 576013 939 Rev D...