background image

     

Page

 

18

B

Backup

E

Enter

C

Change

F

Function

M

Mode

P

Print

S

Step

T

Tank/Sensor

KEY SYMBOLS: 

Press 

until the display shows:

To test individual tanks press 

 

 

 

. To test all tanks press 

 

 the display will show 

To end the test manually press 

 

 

 or to set a duration for the test press 

.

Select the test accuracy, either 0.20 gal/hr or 0.10 gal/hr. To change the setting press 

 

. Press 

 to continue.

Enter the Test Duration in hours, press 

 

. The display will show 

Press 

 to start the test. For individual tanks press 

 to go to the next tank.

Return to normal operating mode: press 

 until the date and time display appears.

F

START IN-TANK LEAK TEST
PRESS <STEP> TO CONTINUE

consoles\qh\44.eps

S

C

E

S

S

S

TEST CONTROL: ALL TANKS
TIMED DURATION

consoles\qh\45.eps

C

E

S

S

C

E

S

E

S

START LEAK TEST TANKS
PRESS <ENTER>

consoles\qh\46.eps

E

T

F

To Start An In-Tank Leak Test

Do not start an in-tank leak test if there has been a 
delivery to the tank to be tested within the previous 

8 hours. This will result in an invalid test.

A delivery to a tank being tested results in an invalid 
test.

Dispensing from a tank being tested will cause a 
Sudden Loss Alarm.

Summary of Contents for TLS-300

Page 1: ...Manual 576013 939 Rev D TLS 300 TLS 350 TLS 350R Operator s Quick Help...

Page 2: ...or use of this publication Veeder Root reserves the right to change system options or features or the information contained in this publication This publication contains proprietary information which...

Page 3: ...loat Discriminating Sensor Alarms 14 Vapor Sensor Alarms 15 Groundwater Sensor Alarms 16 System Status Messages 17 To Start An In Tank Leak Test 18 To Stop In Tank Leak Testing 19 In Tank Leak Test Re...

Page 4: ...I JKL MNO PRS TUV WXY ALARM TEST TANK SENSOR 0 7 8 9 1 2 3 4 5 6 consoles qh US 1 eps ALARM WARNING MMM DD YYYY HH MM XM ALL FUNCTIONS NORMAL Liquid Crystal Display showing normal operating display Al...

Page 5: ...er by successive presses of the key Press once for A Press again for B again for C and a fourth time to enter a 2 The period is on key 1 The decimal point is on the Right Arrow key The zero key has a...

Page 6: ...OLUME 5146 GALS HEIGHT 44 INCHES WATER 0 00 INCHES TEMP 46 8 DEG F INCREASE END MMM DD YYYY HH MM XM VOLUME 8104 GALS HEIGHT 84 INCHES WATER 0 00 INCHES TEMP 47 2 DEG F GROSS INCREASE 2958 TC NET INCR...

Page 7: ...y or for any other specified period The Shift Reconciliation Report is illustrated opposite See also Automatic Reports TO PRINT A RECONCILIATION REPORT Press until the display shows M Press twice and...

Page 8: ...s Manual for complete report printing options such as printing weekly or periodic reports TO PRINT DELIVERY VARIANCE REPORTS Press until the display shows Press until the display shows Press to printo...

Page 9: ...ple at right M RECONCILIATION MODE PRESS FUNCTION TO CONT F BOOK VARIANCE PRESS STEP TO CONTINUE P consoles qh US 76 eps PROD 1 UNLEADED GASOLIN BOOK VARIANCE DAILY MMM DD YYYY HH MM XM VOLUMES ARE ST...

Page 10: ...ERS T1 LEAK TEST RESULTS T 1 UNLEADED GASOLINE PROBE SERIAL NUM 900007 0 20 GAL HR TEST PASS MMM DD YYYY HH MM XM 0 10 GAL HR TEST INVL MMM DD YYYY HH MM XM MONTHLY TANK TEST REPORT T 1 UNLEADED GASOL...

Page 11: ...e console will flash the messages alternately WARNINGS These indicate that an in tank alarm is imminent or that a system fault has occurred ALARMS Alarms indicate a potentially dangerous situation may...

Page 12: ...gh Level Limit Delivery Limit Low Level Limit High Water Limit Water Warning Limit Limit Full Volume Overfill Limit High Level Limit Delivery Limit Low Level Limit High Water Limit Water Warning Limit...

Page 13: ...HH MM XM T1 INVALID FUEL LEVEL IN TANK ALARM T 1 REGULAR UNLEADED INVALID FUEL LEVEL MMM DD YYYY HH MM XM consoles qh US 13 eps CAUSE Fuel and water level floats on the probe are too close together d...

Page 14: ...m by pressing the red ALARM TEST key Arrange a delivery MMM DD YYYY HH MM XM T1 LEAK ALARM IN TANK ALARM T 1 REGULAR UNLEADED LEAK ALARM MMM DD YYYY HH MM XM consoles qh US 18 eps MMM DD YYYY HH MM XM...

Page 15: ...ded a pre set limit during a Leak Test This indicates a possible leak fuel being dispensed or other unauthorized loss ACTION Silence the alarm by pressing the red ALARM TEST key Check that fuel has no...

Page 16: ...ensor shown has detected liquid in the sump being monitored ACTION Silence the alarm by pressing the red ALARM TEST key Investigate the cause of the alarm and take appropriate action CAUSE The sump se...

Page 17: ...sensor at the location shown has detected fuel vapor or liquid ACTION Silence the alarm by pressing the red ALARM TEST key Investigate the cause of the alarm and take appropriate action CAUSE The sens...

Page 18: ...sensor at the location shown has detected fuel vapor in the monitoring well ACTION Silence the alarm by pressing the red ALARM TEST key Investigate the cause of the alarm and take appropriate action C...

Page 19: ...sensor at the location shown has detected fuel ACTION Silence the alarm by pressing the red ALARM TEST key Investigate the cause of the alarm and take appropriate action CAUSE The Groundwater sensor a...

Page 20: ...SE Either the printer release lever is in the down position or the printer is inoperative ACTION Silence the alarm by pressing the red ALARM TEST key Check that the paper release lever is in the up po...

Page 21: ...test For individual tanks press to go to the next tank Return to normal operating mode press until the date and time display appears F START IN TANK LEAK TEST PRESS STEP TO CONTINUE consoles qh 44 eps...

Page 22: ...e test To stop testing all tanks Press The display will show Press to halt the test F STOP IN TANK LEAK TEST PRESS STEP TO CONTINUE consoles qh 48 eps S C E S STOP LEAK TEST TANK X PRESS ENTER console...

Page 23: ...generate the report Press until the normal operating mode display appears F consoles qh 52 eps IN TANK TEST RESULTS PRESS STEP TO CONTINUE P S T P F MMM DD YYYY HH MM XM LEAK TEST REPORT T 1 REGULAR...

Page 24: ...ct the shift and to display inventory data Press to select a different tank Press to print the report F consoles qh 58 eps LAST SHIFT INVENTORY PRESS STEP TO CONTINUE S T P consoles qh US 59 eps SHIFT...

Page 25: ...ime display by pressing until it appears consoles qh US 56 eps MMM DD YYYY HH MM XM ALL FUNCTIONS NORMAL F S consoles qh US 61 eps T 1 REGULAR UNLEADED DELIVERY 2958 GALS T P M MMM DD YYYY HH MM XM T1...

Page 26: ...very Maintenance section of the Operator s Manual for complete instructions and printing options In the Operating Mode press until the display shows Press until the display shows Press until the desir...

Page 27: ...LINES consoles qh US plld2 eps S C E S SELECT TEST TYPE 3 0 GPH consoles qh US plld3 eps This step lets you select 3 0 0 2 or 0 1 gph line leak tests to run on the selected line s If your system does...

Page 28: ...consoles qh US plld7 eps S SELECT LINE ALL LINES consoles qh US plld8 eps E C and the system displays the message Press to stop the test on the line shown or press until you see the line you want to s...

Page 29: ...TO CONTINUE consoles qh US wplld1 eps S SELECT LINE ALL LINES consoles qh US plld2 eps S C E S SELECT TEST TYPE 3 0 GPH consoles qh US plld3 eps This step lets you select 3 0 0 2 or 0 1 gph line leak...

Page 30: ...n press SELECT LINE W WPLLD NUMBER consoles qh US wplld10 eps E C E W TEST ABORTED PRESS STEP TO CONTINUE consoles qh US wplld11 eps F F P WPLLD LINE RESULTS PRESS STEP TO CONTINUE consoles qh US wpll...

Page 31: ...display will show Press to display the date If the date is correct press if not press and enter the correct date Note that the month must be entered first Press the new date will be displayed M consol...

Page 32: ...time is correct press to return to the Operating mode To change the time press and enter the correct time Select either AM or PM by using the arrow keys Press to confirm the time The display will sho...

Page 33: ...printer cover 1 and push the paper feed release lever down If the take up spool has been used pull out the spool with the printed reports and tear off the paper close to the printer feed roller 2 cons...

Page 34: ...Take up Spool place the paper tail between the two halves and press them firmly together until you hear a click 4 4 consoles qh p27b eps Push the Take up Spool into the upper slots Rotate the spool c...

Page 35: ......

Page 36: ...Manual 576013 939 Rev D...

Reviews: