7
In-Tank Setup
Periodic Test Averaging
7-24
Periodic Test Averaging
If necessary, press STEP until you see the message:
When on, Periodic Test Averaging activates averaging for the last five 0.2 gph (0.76 lph) in-tank leak tests. To leave
the feature off, press STEP. (The system displays the TANK TEST NOTIFY message.) To turn on the feature, press
CHANGE and press ENTER. The system displays the message:
Tank Test Notify
If necessary, press STEP until you see the message:
When on, the Tank Test Notify feature triggers a warning, allowing the operator to set a relay to shut down the
submersible. To leave the feature off, press STEP. (The system displays the TNK TST SIPHON BREAK message.)
To turn on the feature, press CHANGE and press ENTER. The system displays the message:
Tank Test Siphon Break
If necessary, press STEP until you see the message:
NOTE: This option requires that the siphon break valve be installed.
When on, Tank Test Siphon Break allows the operator to perform in-tank leak tests on siphon manifolded tanks. To
leave the feature off, press STEP. (The system displays the DELIVERY DELAY message.) To turn on the feature,
press CHANGE and press ENTER. The system displays the message:
Stick Offset
(International Option)
The Stick Offset display appears only if Stick Height Offset was enabled in System Setup (“Stick Height Offset -
International Option” on page 5-14). A Stick Offset can be entered for each tank so that the probe (product)
T1: (Product label)
PER TEST AVERAGING: OFF
PER TEST AVERAGING: ON
PRESS <STEP> TO CONTINUE
T1: (Product Label)
TANK TEST NOTIFY: OFF
TANK TEST NOTIFY: ON
PRESS <STEP> TO CONTINUE
T1: (Product Label)
TNK TST SIPHON BREAK: OFF
TNK TST SIPHON BREAK: ON
PRESS <STEP> TO CONTINUE