8-9
8
In-Tank Leak Tests
CSLD Report Only
CSLD Report Only
If necessary, press STEP until you see the message:
Note: this message only displays if you have selected CSLD as the test frequency.
When enabled this feature inhibits the ‘No CSLD Idle Time’ and ‘CSLD Incr Rate’ alarms, and only prints CSLD
status reports at one of the times selected below:
•
End of Month (at 8:00 a.m.),
•
Day 15 and End of Month (both at 8:00 a.m.), or
•
Day 25 and End of Month (both at 8:00 a.m.)
Press STEP to leave this feature disabled. Press CHANGE until the desired report print time(s) is displayed and
then press ENTER. Press STEP to continue.
Leak Test Report Format
The leak test report format can be set to Normal or Enhanced (select Enhanced to comply with the California Code
of Regulations). The enhanced report will have height, water, temperature, percent volume, rate and threshold
values in addition to the normal report format.
If necessary press STEP until you see the following message:
To accept the displayed format, press STEP. To select the enhanced test format press CHANGE to toggle to
enhanced, then press ENTER to confirm. Press STEP to continue.
Setting Up Additional Tanks
If you are setting up the test for Single Tanks, the setup is complete for the selected tank. To set up additional
tanks, press STEP to return to the TEST SINGLE TANK message:
Then press TANK/SENSOR to choose the next tank. Repeat the setup procedures described above, beginning
with the section titled “Leak Test Frequency” on page 8-2. If you are setting up the test for All Tanks, or have
completed setting up all individual tanks, the setup is complete. Press FUNCTION to exit.
REPORT ONLY: ALL TANK
DISABLED
LEAK TEST REPORT FORMAT
NORMAL
TEST SINGLE TANK: TANK 1
ON DATE