12-3
12
Volumetric Line Leak Detection
Fuel Type
Press STEP to continue.
Fuel Type
If necessary, press STEP until you see the message:
Use this display to specify the type of fuel running through the assigned product line. To accept Gasoline for the
Fuel Type, press STEP. (The system proceeds to the 2” PIPING LENGTH message.) To choose Diesel, press
CHANGE in response to the FUEL TYPE message and press ENTER. The system confirms your choice with the
message:
NOTE: If a fuel other than diesel or gasoline is used, select the type that is closest in viscosity to the fuel that is
being dispensed.
Press STEP to continue.
Piping Length and Type
If necessary, press STEP until you see the message:
To enter the length of 2-inch (50 mm) piping in the line, press CHANGE. Enter the length. Press ENTER. The
system confirms your entry:
Press STEP to display the message that allows you to enter the total length of 3-inch (76 mm) piping in the
system:
To enter the 3-inch piping length, press CHANGE. Enter the length. Press ENTER. The system confirms your entry
with the message:
P#: (Dispense Mode)
PRESS <STEP> TO CONTINUE
P#: (Pipe Label)
FUEL TYPE: GASOLINE
FUEL TYPE: DIESEL
PRESS <STEP> TO CONTINUE
P#: (Pipe Label)
2” PIPING LENGTH: 000
2” PIPING LENGTH: XXX
PRESS <STEP> TO CONTINUE
P#: (Pipe Label)
3” PIPING LENGTH: 000
3” PIPING LENGTH: XXX
PRESS <STEP> TO CONTINUE