15
Pump Sense Setup
Pump Sense Tank Number
15-2
Pump Sense Tank Number
If necessary, press STEP until you see the message:
In this step you assign each connected pump controller (selected above) to the tank in which it is installed (only
configured Pump Sense module inputs will appear). The default value is for this display is NONE. Press CHANGE
until the correct tank number for the first pump controller is visible. Press the TANK/SENSOR key to view the next
pump controller. Press CHANGE to select its correct tank number. Press ENTER to confirm your choice. The
system displays the following message:
Press STEP to display the Enter Dispense Mode screen.
Pump Sense Dispense Mode
If necessary, press STEP until you see the message:
In this step you select the dispense mode of the tank. The choices are:
•
STANDARD - Only one pump feeds the line.
•
MANIFOLDED: ALTERNATE
1,2
- When a dispense starts, the pump in the tank with the greatest inventory
volume will run until the dispense ends. See Auto Active Switchover below for optional selections with this
dispense mode.
•
MANIFOLDED: SEQUENTIAL
1,2
- The tanks are pumped low one at a time. When the tank’s volume drops
below the entered Pump Threshold percentage, pumping will switch over immediately to the next available tank
in the line manifolded set. Pumping will continue from the current tank for another 10 seconds to avoid a
disruption in dispensing during the switch over. (see “Pump Threshold” on page 7-26).
•
MANIFOLDED: ALL PUMPS - All pumps on the line are run.
•
MANIFOLDED: ALTERNATE-HT
1,2
- When a dispense starts, the pump in the tank with the greatest fuel height
will run until the dispense ends. See Auto Active Switchover below for optional selections with this dispense
mode.
1. To prevent backfilling, the level of all tanks connected to the line will be monitored. If the level of any tank exceeds
95% of the Max or Label Volume limit (see “Max or Label Vol” on page 7-16), the pump for that tank will also be
turned on during dispensing. The state of the pump that was already ON will not be changed.
2. At locations with manifolded fuel lines that have a mechanical line leak detector installed for each pump, the TLS
Console must be programmed for either Manifolded: Alternate, Manifolded: Alternate-HT or Manifolded:
Sequential. Doing so ensures that each line meets the 3 GPH requirement.
SX: SELECT TANK
NONE
T#: [Product Label)
PRESS <STEP> TO CONTINUE
S1: ENTER DISPENSE MODE
STANDARD