22
3-Wire C.L. Sensor Setup
3-Wire C.L. Sensor Location
22-2
module until you have entered the configuration information (sensor positions) for all modules and the system
displays the ENTER SENSOR LOCATION message.
3-Wire C.L. Sensor Location
If necessary, press STEP until you see the message:
To enter the sensor location, press TANK/SENSOR repeatedly until the sensor you want appears on the second
line of the message (H1, H2, etc.). Press CHANGE and enter the sensor location (up to 20 alphanumeric
characters) of the selected sensor. A typical entry is: DISPENSER PAN PUMP, etc. (This information appears on
sensor status and sensor alarm reports to make it easier to identify the location of the alarm.) Press ENTER to
confirm your entry:
Press STEP to continue.
3-Wire C.L. Sensor Mode
If necessary, press STEP until you see the message:
Use this display to identify the selected sensor’s mode, so the system can properly interpret and report sensor
information. You can choose Standard mode or High Vapor mode. In Standard mode, the sensor alarms when it
senses any hydrocarbon, liquid, or vapor along the length of the sensor. In High Vapor mode the sensor alarms
only if it detects
both
liquid hydrocarbon
and
an extremely high hydrocarbon vapor. This mode is recommended
ONLY if the sensor has recently detected a leak and hydrocarbon residue may still be on the sensing element.
To choose Standard mode, press STEP. (The system displays the CATEGORY message.)
To choose High Vapor, press CHANGE in response to the ENTER SENSOR MODE message. Press ENTER to
confirm your choice:
Press STEP to continue.
3-Wire C.L. Sensor Category
If necessary, press STEP until you see the message:
If necessary, press CHANGE until you see the correct category. The category options are:
ENTER SENSOR LOCATION
H1:
H1: (Sensor Location)
PRESS <STEP> TO CONTINUE
H1: ENTER SENSOR MODE
STANDARD
H1: (Sensor Mode)
PRESS <STEP> TO CONTINUE
H1: (Sensor Location)
CATEGORY:OTHER SENSORS