5
System Setup
Line Re-Enable Method
5-10
Press STEP. The system displays the message:
The default value is 355 days. If you do not want to accept the default, press CHANGE. Enter the number of days
after which you want the system to alarm if a test has not been passed (0 to 365). This number should be higher
than the number you set for periodic warning. Press ENTER. The system displays the message:
Press STEP. (The system displays the Line Re-Enable Method message.)
DISABLE TANK ANNUAL TEST NEEDED WARNINGS AND ALARMS
To disable Tank Annual Test Needed Warnings that are already enabled, press CHANGE in response to the Tank
Annual Test Needed Warnings Enabled message and press ENTER. The system confirms your choice with the
message:
Press STEP continue. (The system displays the Line Re-Enable Method message.)
Line Re-Enable Method
If necessary, press STEP until you see the message:
This feature lets you choose how to re-enable a line shut down by a failing line leak test. To re-enable a shutdown
line only by a passed line test, press STEP. (The system displays the Line Periodic Test Needed Warning.)
To re-enable a shutdown line by acknowledging the alarm that caused the shutdown, press CHANGE and the
system displays the message:
Press ENTER to confirm the choice and STEP to continue.
Line Periodic Test Needed Warnings
If necessary, press STEP until you see the message:
The system monitors the amount of time since the last passed 0.2 gph (0.76 lph) line test. By enabling Line
Periodic Test Needed Warnings, you can have the system provide a warning when a line test has not been passed,
TANK ANN TST NEEDED ALM
DAYS = XXX
DAYS = XXX
PRESS <STEP> TO CONTINUE
DISABLED
PRESS <STEP> TO CONTINUE
LINE RE-ENABLE METHOD
PASS LINE TEST
LINE RE-ENABLE METHOD
ACKNOWLEDGE ALARM
LINE PER TST NEEDED WRN
DISABLED