5
System Setup
Maintenance History
5-18
2. Press CHANGE in response to the first SYSTEM SECURITY CODE message. Enter any six digits for your
code and press ENTER. The system confirms your entry with the message:
Maintenance History
The Maintenance Report feature is available in the TLS-350 with version 27 software and a NVMEM 203 card
installed.
Press STEP to display the message:
This feature maintains a rolling 3 year history of the following maintenance records:
•
Active Alarm (alarm post) – alarm type and number, device number, active date/time. This includes protected
maintenance alarms.
•
Inactive Alarm (alarm clear) – alarm type and number, device number, inactive date/time. This includes protected
maintenance alarms.
•
Maintenance History enable - date/time of enable
•
Maintenance History disable –date/time of disable
•
Service codes – service code, date/time entered (Note: Service codes can be found in the Maintenance
Service Code Quick Help (P/N 577013-874)
•
Last Monthly Fullest Periodic Tank Test Passed – tank number, start date/time
•
Last Monthly PLLD 0.2 GPH Test Passed – tank number, date/time entered (record added at 1st of month)
•
Last Monthly WLLD 0.2 GPH Test Passed – tank number, date/time entered (record added at 1st of month)
•
Last Monthly VLLD 0.2 GPH Test Passed – tank number, date/time entered (record added at 1st of month)
The default for this feature is DISABLED. Press CHANGE, then ENTER to change the default to ENABLED.
Tank Chart Security
If necessary, press STEP until you see the message:
CODE: XXXXXX
PRESS <STEP> TO CONT
MAINTENANCE HISTORY
DISABLED
TANK CHART SECURITY
PRESS <ENTER>