In-Tank Setup
Leak Minimum Annual
7-22
To enter a Leak Minimum Periodic value for the selected tank, press CHANGE. Enter the percent value and press
ENTER to confirm your entry. The system displays:
Leak Minimum Annual
If necessary, press STEP until you see the message:
This value tells the system the minimum tank volume required to record a passed annual test. The value reflects
federal, state, and local requirements.
To enter a Leak Minimum Annual value for the selected tank, press CHANGE. Enter the percent value and press
ENTER to confirm your entry. The system displays:
Periodic Test Type
If necessary, press STEP until you see the message:
You can choose between Standard and Quick. Choose Standard to run a 2-hour periodic leak test. Choose Quick
to perform a 0.2 gph (0.76 lph) test in one hour.
To choose Standard, press STEP. (The system displays the ANNUAL TEST FAIL message.) To choose Quick,
press CHANGE, then press ENTER. The system displays the message:
Annual Test Fail
If necessary, press STEP until you see the message:
LEAK MIN PERIODIC: XXX%
PRESS <STEP> TO CONTINUE
T1: (Product Label)
LEAK MIN ANNUAL: 000%
LEAK MIN ANNUAL: XXX%
PRESS <STEP> TO CONTINUE
T1: PERIODIC TEST TYPE
STANDARD
QUICK
PRESS <STEP> TO CONTINUE
T1: ANNUAL TEST FAIL
ALARM DISABLED