5-9
5
System Setup
Tank Annual Test Needed Warnings
DISABLE TANK PERIODIC TEST NEEDED WARNINGS
To disable Tank Periodic Test Needed Warnings, press CHANGE in response to the Tank Annual Test Needed
Warnings Enabled message. The system now displays:
Press ENTER. The system confirms your choice with the message:
Press STEP to continue. (The system displays the Tank Annual Test Needed Warnings message.)
Tank Annual Test Needed Warnings
If necessary, press STEP until you see the message:
The system monitors the amount of time since the last passed 0.1 gph (0.38 lph) tank test. By enabling Tank
Annual Test Needed Warnings, you can have the system provide a warning when a 0.1 gph (0.38 lph) tank test
has not been passed or conducted in a specified number of days (0 to 365) and activate an alarm if a test has not
been passed after a warning, or a specified number of days.
To keep Tank Annual Test Needed Warnings disabled, press STEP. (The system displays the Line Re-Enable
Method message.)
ENABLE TANK ANNUAL TEST NEEDED WARNINGS AND ALARMS
To enable Tank Annual Test Needed Warnings, press CHANGE. The system now displays:
Press ENTER. The system confirms your choice with the message:
Press STEP. The system now displays:
Press CHANGE and enter the number of days after which you want the system to warn that a 0.1 gph (0.38 lph)
tank test has not been passed (0 to 365). Press ENTER. The system displays the message:
TANK PER TST NEEDED WRN
DISABLED
DISABLED
PRESS <STEP> TO CONTINUE
TANK ANN TST NEEDED WRN
DISABLED
TANK ANN TST NEEDED WRN
ENABLED
ENABLED
PRESS <STEP> TO CONTINUE
TANK ANN TST NEEDED WRN
DAYS = XXX
DAYS = XXX
PRESS <STEP> TO CONTINUE