Operation
PMC Alarm Summary
PMC Alarm Summary
Table 2 contains a listing of the PMC generated alarms including their displayed message and cause. TLS
Console PMC alarms may be interspersed amongst non-PMC alarms, please see TLS350 Series manuals for
more information.
Table 2. TLS 350 (PMC) Alarm Troubleshooting Summary
Message
(Definition)
Severity
Level
Light
Indicator
Suggested
Troubleshooting
Warn after first
30-minute runtime
Yellow
VP RUNTIME FAULT
To notify that the
Processor has
continuously run for
longer than 30 minutes
Fail after 2
nd
consecutive
30-minute runtime
Red
• TLS-350 PMC Variable setup
Confirmation Procedure: Section 16
• EO-VR-203: Exhibit 8
• TP-201.3 and
EO-VR-203
: Exhibit 4
• EO-VR-203: Exhibit 9
• VST Troubleshooting Manual 9514-003
(found at
www.vsthose.com
)
•
VST ASC Level C
Warn on the first
day
Yellow
VP EMISSIONS
To notify when the mass
emissions exceeds the
defined threshold for the
system
Fail on consecutive
days
Red
• TLS-350 PMC Variable setup
Confirmation Procedure
• EO-VR-203: Exhibit 6
• VST Troubleshooting Manual 9514-003
(found at
www.vsthose.com
)
• VST ASC Level C
Warn on the first
day
Yellow
VP PRESSURE
To notify when 10% of the
daily pressure-data is equal
to or exceeds 1” WC.
Fail on consecutive
days
Red
• TLS-350 PMC Variable setup
Confirmation Procedure
• EO-VR-203: Exhibit 8
• EO-VR-203: Exhibit 9
• VST Troubleshooting Manual 9514-003
(found at
www.vsthose.com
)
• VST ASC Level C
Warn on the first
day
Yellow
VP DUTY CYCLE
To notify when the duty
cycle exceeds 18 hours per
day or 75% of a day
Fail on consecutive
days
Red
• TLS-350 PMC Variable setup
Confirmation Procedure
• EO-VR-203: Exhibit 9
• TP-201.3 and EO-VR-203: Exhibit 4
• VST Troubleshooting Manual 9514-003
(found at
www.vsthose.com
)
• VST ASC Level C
Section 16
Pressure Management Control