Operation
Viewing PMC Reports Via RS-232 Connection
Figure 13. Vapor Processor Status Report Details - Serial to PC Format
<SOH>
IV8200
JUN 1, 2002 8:07 AM
(SITE NAME)
(SITE STREET)
(CITY, STATE)
(PHONE
NUMBER)
VAPOR PROCESSOR STATUS REPORT
PMC VERSION: 01.00
VAPOR PROCESSOR TYPE: VST VAPOR PROCESSOR
PMC MONITORING TEST PASS/FAIL THRESHOLDS
PERIOD BELOW ABOVE
VAPOR PROCESSOR PRESSURE FAIL, 90th PERCENTILE 1DAYS ---- 1.00 INCHES
H2O
VAPOR PROCESSOR MASS EMISSION FAIL 1DAYS ---- 0.64 LBS/1KG
VAPOR PROCESSOR DUTY CYCLE FAIL 1DAYS ---- 75.00 %
VP OVER PRESSURE TEST : PASS (0.03 INCHES H2O)
EFFLUENT EMISSIONS TEST : PASS (0.32 LBS/1KG)
VP DUTY CYCLE TEST : PASS (17.54%)
VP INPUT STATUS : NOTEST
RUN TIME HOURS : 4.2
DAILY THROUGHPUT : 8421 GALS
AVG HC PERCENT : 8.85 %
Section 16
Pressure Management Control