  Diagnostics

Automatic Control and Runtime Fault Alarm

Under automatic control, vapor pressure readings are compared to user programmable thresholds to determine 
the appropriate Pressure Management Device (PMD) state. When the PMD is off and the OVERPRESSURE 
LIMIT is exceeded, an internal relay is enabled and remains so until the pressure drops below the TURN OFF 
VAPOR PROCESSOR threshold. Automatic control is the default mode.

Manual control 

If PMC mode is Manual, the diagnostic menu allows the PMD to be directly turned on/off through the relay. This 
feature is to support unit operational testing without waiting for the pressure to hit limits. The current UST ullage 
space vapor pressure will also be available through the diagnostic menu. The VC1 RS232 command allows for 
remote control of the PMD when the PMD control is manual. Note: If the PMD is on and the PMC mode is 
Automatic, changing the control mode to Manual mode will turn the PMD off.

PMC Diagnostic Menu

Figure 16.  PMC Diagnostic Menus

PMC VERSION: 01.00
PRESS <STEP> TO CONTINUE

S

S

VAPOR PRESSURE
INCHES H2O:       -x.xxx

S

VAPOR PROCESSOR MODE
AUTOMATIC

<CHANGE>  selects
AUTOMATIC (default) / MANUAL

S

VAPOR PROCESSOR STATE
VP STATE: OFF

If VP mode = MANUAL, and relay
configured Then, <CHANGE> 
selects ON / OFF

S

HYDROCARBON SENSOR
HC SENSOR: XX.XXX%

S

CLEAR TEST AFTER REPAIR
PRESS <ENTER>

PROCESSOR STATUS TEST
PRESS <ENTER>

S

CLEAR TEST AND LOG
ARE YOU SURE? NO

S

pmcfig4.eps

Prints out a copy of the 
PMC Diagnostic report. 
See example at right.

C

F

P

S

T

Change

E

Enter

Function

Print

M

Mode

Step

Tank/Sensor

Key press
sequence

Repress until
desired message
appears in display

Key Legend

1

2

PMC DIAGNOSTICS

---------------------- 

PMC VERSION: 01.00

VAPOR PROCESSOR MODE

AUTOMATIC

VAPOR PROCESSOR STATE

VP STATE ON

 

PMC DIAGNOSTIC
PRESS <STEP> TO CONTINUE

DIAG MODE

PRESS <FUNCTION> TO CONT

M

P

F

Section 16

Pressure Management Control

16-19

Summary of Contents for TLS-350R

Page 1: ...Manual No 577013 801 Revision A Install Setup Operation Manual Pressure Management Control Section 16 Pressure Management Control 16 i...

Page 2: ...tailed description of the damage on the face of the freight bill The carrier s agent must verify the inspection and sign the description 2 Immediately notify the delivering carrier of damage or loss T...

Page 3: ...a period of one 1 year from the date of installation or twenty four 24 months from the date of invoice whichever occurs first During the first ninety 90 days we or our representative will repair or re...

Page 4: ...and Runtime Fault Alarm 19 Manual control 19 PMC Diagnostic Menu 19 Figures Figure 1 TLS console Interface Module Bays 3 Figure 2 Smart Sensor Setup 5 Figure 3 PMC Setup 6 Figure 4 TLS console alarm...

Page 5: ...Port will be available for use by contractor or government inspectors Contractor Certification Requirements Veeder Root requires the following minimum training certifications for contractors who will...

Page 6: ...is sup plied to the device A potential shock hazard exists TURN POWER OFF Live power to a device creates a potential shock hazard Turn Off power to the device and associ ated accessories when servicin...

Page 7: ...which interface modules can be installed Comm bay Power bay and Intrinsically Safe bay ref Figure 1 Probe Interface modules and Smart Sensor modules are installed in the Intrinsically Safe bay and the...

Page 8: ...em Grounding Probe and Sensor Shields Connect probe and sensor cable shields to ground at the console only Do not ground both ends of the shield CIRCUIT DIRECTORY A circuit directory is adhered to the...

Page 9: ...ECT SS CATEGORY UNKNOWN C C E S E S E S P F SMARTSENSOR SETUP PRESS STEP TO CONTINUE SETUP MODE PRESS FUNCTION TO CONT M P C C C F P S T Change E Enter Function Print M Mode Step Tank Sensor Key press...

Page 10: ...tes after start time Data collected 5 minutes before the Start of Test time is omitted from test S SET ANALYSIS TIME PRESS ENTER E S SET TEST START TIME TIME hh mm SET POST DELAY DURATION DELAY MINUTE...

Page 11: ...rm messages The system automatically prints an alarm report showing the alarm type its location and the date and time the alarm condition occurred Warning and alarm posting causes the TLS console base...

Page 12: ...ime the alarm was posted Alarm example in Figure 6 PMC Alarms are logged into the Priority Alarm History in the TLS Figure 6 TLS console alarm example MMM DD YYYY HH MM XM VP EMISSIONS WARN PMC ALARM...

Page 13: ...VST ASC Level C Warnonthefirst day Yellow VP EMISSIONS To notify when the mass emissions exceeds the defined threshold for the system Failonconsecutive days Red TLS 350PMCVariablesetup ConfirmationPr...

Page 14: ...YY HH MM SS XM ALL FUNCTIONS NORMAL S S S S EFFLUENT EMISSIONS TEST STATUS PASS S VP DUTY CYCLE TEST STATUS PASS pmc fig7 eps Prints out a copy of the PMC Status report See example at right C F P S T...

Page 15: ...S 232 board DB25 female Slots 1 2 or 3 ATEN USB to DB9 serial adapter P N 576040 170 Serial I O PC Card Plugs into PCMCIA port Multiport board DB9 female Slot 4 Laptop TLS 350R TLS 350R USB male lapto...

Page 16: ...tton you may see a repeat of the modem dialing windows in which case ignore cancel them all 4 When the Connect To window appears Figure 10 depending on your connection method select either COM1 If RS...

Page 17: ...disabled If the code was enabled you would see a 6 digit number which you will need to enter to access the console refer to the Sending Console Commands paragraph below for more information SETUP MOD...

Page 18: ...o the main screen If the RS 232 Security Code is disabled press and hold the Ctrl key while you press the A key then type in IV8200 If the RS 232 Security Code is enabled e g 000016 you must enter the...

Page 19: ...ocessor Status Report See example Figure 13 SOH IV8200 Vapor Processor Runtime Diagnostic Report See example Figure 14 SOH IV8000 Percent Hydrocarbon Diagnostic Report See example Figure 15 SOH IV8100...

Page 20: ...SSOR PMC MONITORING TEST PASS FAIL THRESHOLDS PERIOD BELOW ABOVE VAPOR PROCESSOR PRESSURE FAIL 90th PERCENTILE 1DAYS 1 00 INCHES H2O VAPOR PROCESSOR MASS EMISSION FAIL 1DAYS 0 64 LBS 1KG VAPOR PROCESS...

Page 21: ...5 NO 3 09 07 1 15PM 17 92 0 278 0 268 NO 3 10 07 3 01AM 7 70 0 200 0 223 NO 3 10 07 4 30AM 4 02 0 202 0 224 NO 3 10 07 7 54PM 23 62 0 306 0 245 NO 3 11 07 11 24PM 6 55 0 256 0 213 NO 3 12 07 11 31PM 2...

Page 22: ...M 1 042 8 25 07 7 57AM 1 040 8 25 07 7 57AM 1 040 8 25 07 7 57AM 1 032 8 25 07 7 57AM 1 030 8 25 07 7 56AM 1 050 8 25 07 7 56AM 1 040 8 25 07 7 56AM 1 040 8 25 07 7 56AM 1 032 8 25 07 7 55AM 1 050 8 2...

Page 23: ...anual Note If the PMD is on and the PMC mode is Automatic changing the control mode to Manual mode will turn the PMD off PMC Diagnostic Menu Figure 16 PMC Diagnostic Menus PMC VERSION 01 00 PRESS STEP...

Page 24: ...For technical support sales or other assistance please visit www veeder com Section 16 Pressure Management Control 16 20...

Reviews: