TLS-450 Setup and Operation Screens Manual
354
Maintenance Operation
When to Perform
What To Do
sensor in its upright position, the
system should activate a 'FUEL
ALARM'. Turn the sensor upside
down to be sure the system
activates a 'WATER ALARM'. If the
sensor does not alarm in both
conditions, replace the sensor.
2. Verify epoxy kits have been installed
on field wiring.
3. Replace sensor if cable is cracked
or damaged (ref. item A.1).
Mag Sensor
Yearly
A. Owner or Station Attendant
1. Inspect sensor cable for any
cracking or damage.
2. Check that sensor is resting firmly
on bottom of monitored pan/sump.
B. Service Contractor
1. Replace Mag Sensor cable if
cracked or damaged (ref. item A.1).
2. Verify epoxy kits have been installed
on field wiring.