TLS-450 Setup and Operation Screens Manual
56
Printout example notes:
1. The '<' (drop below) or '>' (rise above) symbols in the printout example indicate the point
(threshold) at which the Alarm/Warning will be triggered.
2. The Programmable column indicates if the Alarm/Warning threshold is or is not programmable.
3. The Upgrade column indicates if the Alarm/Warning's Alarm Delay feature (see field below) is
activated.
4. The Water Warning has an programmable Alarm Delay that was set to 48 hours.
Configured
Allowable selections: Enabled, Disabled
Default: Disabled
Address
Allowable selections: Choose from drop-down list of available Mag sensors, Not Assigned
Default: Not Assigned
Label
Allowable selections: Up to 20 alphanumeric characters
Default: Blank
Serial Number
This is a read-only entry of the selected Mag Sensor's serial number.
Alarm Delay
This display appears if the alarm delay has been factory set to programmable. This is the time in hours
following the triggering of uncleared warnings, before they are upgraded to alarms. Also, this upgrade
only applies to Mag Sensor warnings that have been factory set to upgrade.
Allowable selections: 0-9999 Hours
Default: Assigned by sensor
Water Warning
This display appears only if the Water Warning has been factory set to programmable. This is the height
in inches (or mm if metric units selected) at which the Water Warning will activate.
Allowable selections: 1.7 - 22 in. (44 - 558mm)
Default: 0
Water Alarm
This display appears only if the Water Alarm has been factory set to programmable. This is the height in
inches (or mm if metric units selected) at which the Water Alarm will activate. Refer to your Smart Sensor
Setup printout's Min/Max Thresholds for the permissible range within which to select this value.
Allowable selections: 1.7 - 22 in. (44 - 558mm)
Default: 0