Setup
Vapor Recovery Setup
General
Touch General to access the Vapor Collection General setup screen (Figure 16).
Figure 16. Example Vapor Collection General Setup Screen
Configure the following fields depending on the site’s EVR Type selection:
• EVR Type - Balance (default) or Assist
• Balance Type - This field is only available when the EVR Type is set to Balance. Choices are VST
• Assist Type - This field is only available when the EVR Type is set to Assist. Choices are Vapor Vac, Wayne
Vac, Healy Vac.
• Accept High ORVR - Enabled or Disabled (default). If the ‘Estimated ORVRS >> EXPECTED’ message is
posted to the Miscellaneous Event Log, then set to Enabled.
• Nozzle Type - VST (default) - This field is only available when the EVR Type is set to Balance. Choices are:
VST
• A/L Range Max - This is the upper limit of the A/L ratio operating range of the nozzle. This field is only
populated when the EVR Type is set to Assist. This limit is 1.15 and is not programmable. When the EVR
Type is set to Balance this field is blank.
• A/L Range Min - This is the Lower limit of the A/L ratio operating range of the nozzle. This field is only
populated when the EVR Type is set to Assist. This limit is 0.95 and is not programmable. When the EVR
Type is set to Balance this field is blank.
Touch the check button
to save your choices.