Initial Setup Of The Console Using Workflow Wizard
Setup>BIR>General
24
Setup>BIR>General
In this screen you set up reconciliation para
m
eters for your inventory reports if the BIR
function is enabled (ref. “Meter Data Present” on page 26).
Product Threshold Alarm
Touch to enable an alar
m
that is triggered when your periodic reconciliation data exceeds a
preset product threshold value (see Setup > BIR > Threshold Alar
m
s for details about this
alar
m
).
Daily Close Time
Touch to enter a ti
m
e when you want the syste
m
to store the data for the current day
(default is 02:00 AM).
BIR needs approxi
m
ately 2-5
m
inutes of quiet ti
m
e to generate a report. Because 2:00 AM is
nor
m
ally the quietest ti
m
e of the day, we reco
mm
end using that ti
m
e (unless there is a busi-
ness need to do it at another ti
m
e).
Week Close Time
Touch to enter the Day of the week when you want the syste
m
to store the data for the cur-
rent week (used in weekly reports.
Alarm Threshold Delivery Type
Touch to select how the BIR variance a
m
ount is calculated:
•
Standard
- does not use delivery receipts in the BIR variance a
m
ount calculation.
•
Ticketed Delivery
- uses delivery receipts in the BIR variance a
m
ount calculation. Select
this if the ticketed delivery feature is enabled in the Setup>Delivery screen.
Temperature Compensation
Touch to enter the
m
ethod for calculating BIR volu
m
es:
•
Standard
- use when the
m
eters are not te
m
perature
co
m
pensated (TC).
•
TC Volume
- use when
m
eters are te
m
perature co
m
pen-
sated (TC).
Meter Calibraton Offset %
If you have
m
eters that require a calibration offset, use this
field to enter a
m
eter calibration % to co
m
pensate (applies
to all dispenser
m
eters and is used in the calculated dis-
pensed a
m
ount). For
m
ost do
m
estic (US) sites, the default of
0% is fine.
BIR Daily Close Warning Enable
Touch the radio button to enable or disable the posting of
this warning when the BIR daily close cannot occur at the
scheduled ti
m
e.
BIR Status Warning Enable
Touch the radio button to enable or disable the posting of
this warning when conditions occur that
m
ay i
m
pact the rec-
onciliation variance (such as
m
eter
m
ap inco
m
plete,
m
eter
m
ap unstable, invalid fuel height, probe out, tank chart
changed, DIM queue overrun).
BIR Shift Enable
Touch the radio button to enable or disable the posting of
this warning when the BIR shift close cannot occur at the
scheduled ti
m
e (a BIR shift close could be delayed when a
delivery is in progress, a dispense is in progress, the station