Initial Setup Of The Console Using Workflow Wizard
Setup>Tank>All Tanks
36
Setup>Tank>All Tanks
This screen lets you configure para
m
eters that apply across all tanks in the syste
m
.
User Ullage
Touch radio button to enable or disable the display of the User Ullage field (as can appear in
Overview>Tank Overview and Inventory Reports).
NOTE:
• The regular Ullage Volu
m
e field is displayed on
m
ost console screens, and is calculated by
taking the Max Volu
m
e field in the “Setup>Tank>Li
its” screen and subtracting the vol-
u
m
e of fuel currently in the tank. This result represents the total a
m
ount of e
m
pty space in
the tank.
• The User Ullage field is an additional infor
m
ational field that calculates ullage using a per-
centage of the Ullage Volu
m
e field. User Ullage can be used as a cross-check for deliveries
to
m
ake sure you do not overfill a tank. In so
m
e regions, the ullage is set to between 50
and 100% of the tank (see field below). By setting the ullage to a lower percentage, it adds
an additional buffer so the tank will not be overfilled.
User Ullage%
[Field available only if User Ullage field is enabled]
Touch to enter a percent (fro
m
50 to 100%) of ullage volu
m
e to display.
Print TC Volumes
Touch radio button to enable or disable the printing of te
m
perature co
m
pensated (TC) vol-
u
m
es in screens or reports (inventory, delivery, etc.).
TC Reference
Te
m
perature co
m
pensated (TC) reference te
m
perature for all volu
m
e calculations, and is
location-specific. So
m
e co
mm
on values:
• U.S. 60°F • Canada 15°C
NOTES:
• All leak test calculations are based on the TC reference value that you enter in this field.
• If you do not enable the Print TC Volu
m
es field above, TC values will not appear in the
screens.
• To use TC values, your probe
m
ust support te
m
perature
m
easure
m
ent capabilities.
• If BIR is being used and the
m
eters reporting the sales are te
m
perature co
m
pensated, the
value you enter
m
ust
m
atch the
m
eters' reference te
m
perature value. Also, in
“Setup>BIR>General”, the TC Reference field
m
ust be set to TC Volu
m
e.
C
S
LD Evaporation Reid Vapor Pressure Chart
This field, when enabled, lets you enter Reid Vapor Pressure (RVP) values used by CSLD.
Enabling RVP allows you to enter evaporation co
m
pensation values for each
m
onth for non-
diesel tanks at the site.
This field is enabled if the following fields are set up in “Setup>Tank>Environ
Tank Test Method is set to
CSLD,
Cli
m
ate Factor is set to
Extreme
and
CSLD Evap. Co
m
-
pensation is set to
Enabled.
Entering Values for the CSLD Evaporation
RVP Chart
Once enabled (see above) and you select inside the RVP field
box, a popup window appears that lets you view or enter
RVP entries for each
m
onth of the year. Enter values for each
m
onth field. touch
to save your entries when done.
NOTE:
CSLD evaporation co
m
pensation will use the RVP val-
ues fro
m
your entries for the applicable
m
onth. The console
does not provide evaporation co
m
pensation during
m
onths
having a RVP value of 0 (zero). The RVP
m
onthly values for
your geographical area can be obtained fro
m
your local
Petroleu
m
Distributor or is located on the delivery bill of lad-
ing.
Periodic Test Needed Warnings
Touch radio button to enable or disable the console to post a
warning or an alar
m
after a specified nu
m
ber of days have
passed (0 - 30 days) since the last 0.2 gph (0.76 lph) leak test
was run or successfully passed. The subsequent two fields
relate to this function:
Days Before Periodic Alarm
Post an alar
m
when the test did not successfully pass after a
warning, or if the test was not conducted in a specified nu
m
-
ber of days.
Days Before Periodic Warning
Post a warning when the test did not successfully pass, or if
the test was not conducted in a specified nu
m
ber of days.
Annual Test Needed Warnings
Touch radio button to enable or disable the console to post a
warning or an alar
m
after a specified nu
m
ber of days have
passed (0 - 365 days) since the last 0.1 gph (0.38 lph) leak
test was run or successfully passed. The subsequent two
fields relate to this function:
Days Before Annual Alarm
Post an alar
m
when the test did not successfully pass after a
warning, or if the test was not conducted in a specified nu
m
-
ber of days.
Days Before Annual Warning
Post a warning when the test did not successfully pass, or if
the test was not conducted in a specified nu
m
ber of days.
TC Density
Touch radio button to enable or disable TC density readings
for inventory reports.
NOTE:
This should only be enabled if the site is equipped
with a Mag Plus Probe with a density float syste
m
.
S
tick Height
Enables or disables the Stick Height fields that co
m
pensate
for any difference between a stick
m
easure
m
ent and the
probe
m
easure
m
ent (no tilt). The difference is due to the
stick and the probe
m
easuring slightly different locations in
a tilted tank since the riser used for the stick
m
easure
m
ent
is different than the riser used for the probe.
The stick height offset is set in “Setup>Tank>General”.
When enabled, the calculated stick heights are visible in
Tank Detail.
Stick height is not used for volu
m
e calculation; it is for dis-
play only.