Initial Setup Of The Console Using Workflow Wizard
Setup>Tank>Environmental Test
30
Setup>Tank>Environmental Test
This screen provides a choice of selecting a tank test
m
ethod (SLD, CSLD, or Disabled) for a
selected tank. Once a tank test
m
ethod has been chosen, the corresponding setup para
m
e-
ters for either SLD or CSLD are displayed, and you can enter settings by which the selected
test will be conducted.
Tank Test Method
Select the
m
ethod for testing your tanks:
•
SLD
(Static Leak Detection) - a single tank test (that runs on de
m
and, at a progra
mm
ed
ti
m
e, or by pu
m
p sense signal) where there
m
ust be no dispensing during the test.
•
CSLD
(Continuous Statistical Leak Detection) - leak tests that are run continuously during
idle tank ti
m
es.
•
Disabled
- no testing
m
ethod has been enabled.
SLD
Leak Test Rate
Touch to select which leak rate test is printed:
• 0.2 gph (0.76 lph) Leak Test
• 0.1 gph (0.38 lph) Leak Test
NOTE:
Both of the above tests, as well as the Gross Leak Test [(1.5 gph (5.8 lph)], are run
when you start the SLD tank test. This field deter
m
ines what the syste
m
prints out for the
test results.
Periodic Test Type
Touch to select a periodic test type:
• Standard - Syste
m
runs the periodic leak test for the entire test duration before posting a
test result. The
m
ini
m
u
m
wait ti
m
e after delivery when a test can be run is 8 hours, and
the
m
ini
m
u
m
test duration is 2 hours.
• Quick - Syste
m
runs the periodic leak test for the entire test duration before posting a test
result. The
m
ini
m
u
m
wait ti
m
e after delivery when a test can be run is 5 hours, and the
m
ini
m
u
m
test duration is 1 hour.
Test Frequency
Touch to select the frequency for SLD tests as described
below. Most local agencies require a
m
ini
m
u
m
m
onthly (30
days) test.
Gross Test Auto-Confirm
Touch to enable or disable the ability of the console to
require two failed Gross Tests [(1.5 gph (5.8 lph)] before it
considers the test a failure. NOTE: When enabled, this fea-
ture
m
ay reduce false alar
m
s.
Duration
Touch to enter the a
m
ount of ti
m
e (in hours, fro
m
2 - 24) for
the test to co
m
plete.
Leak Min. Periodic (% Full Volume)
Touch to enter a
m
ini
m
u
m
tank volu
m
e required to record a
valid periodic test (value reflects federal, state, and local
require
m
ents)
Field Range,
Min,
Max
Default Visible
If:
Period
On Date, Annually by
Day of Week,
Monthly by Day of
Week, Weekly, Daily,
Annually by Day of
Month, Monthly by
Day of Month, Auto
On Date
Always
Set Date
Month: 1-12, Day: 1-
31, Year: 1970 - 2038
Current
Date
If Period choice is On
Date
Month
January - Dece
m
ber January
If Period choice is
Annually by Day of Week,
Annually by Day of Month
Weekday
Sunday - Saturday
Sunday
If Period choice is
Annually by Day of Week,
Monthly by Day of Week,
Weekly
Occurrence
1st, 2nd, 3rd, 4th,
Last
1st
If Period choice is
Annually by Day of Week,
Monthly by Day of Week
Day of Month 1 - 31
1
If Period choice is
Annually by Day of Month,
Monthly by Day of Month
Ti
m
e of Day
Ti
m
e in Hours and
Minutes, 12 Hr.
sensitive
Current ti
m
e
+ 2
m
inutes
If Period choice is On
Date, Annually by Day of
Week, Annually by Day of
Month, Monthly by Day of
Week, Monthly by Day of
Month, Weekly, Daily