Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF)
TLS-IB Specifications
4-13
5.
Replace the board by reversing the above steps.
6.
Switch On power to the TLS-IB and check your system configuration for proper setup.
NEURON SERVICE SWITCH
To manually transmit the TLS-IB neuron ID, press S1 (service switch) shown in Figure 4-9. The figure also locates
the IFSF LED (D1) which indicates if the neuron application is, or is not, running. If the IFSF status indication LED
(D1) remains lit, replace the CPU board (see “Replacing the CPU Board” on page 4-8).
Figure 4-9. Manually Transmitting Neuron ID
TLS-IB Specifications
PHYSICAL SPECIFICATIONS
• Width w/door closed: 188 mm (7.6”) - Width w/door open: 235 mm (9.6”).
• Height: 163 mm (6.7”).
• Depth w/door closed: 50 mm (2.6”), Depth w/door open: 228 mm (9”).
• Weight: 1.8 kg (3.5 lbs).
• The TLS-IB unit contains two PC boards: CPU (in door) and Power Supply (in unit).
• Removable plug type connections.
• Conduit knockouts for intrinsically-safe wiring: 1/2”, 3/4”, and 1” I.P.S. (2 places).
SGL DBL
B
A
WIRING SIDE
G
J4
D1
LED1
IFSF
JP3
J8
U8
J7
L1
S1
SERVICE
RAM
tlsnt\ifver.eps
IFSF
CLR
N
M
L
C
L
R
R12-001
331470
R12-002
R12-003
R12-004
R12-005
R12-006
Pressing S1, lights the IFSF
LED (D1) and forces node
to transmit its Neuron ID.
Transmit Neuron ID
Transmit Neuron ID
The Amber IFSF LED (D1)
should not be lit when the
neuron application is running.
This LED remains lit if the
neuron is in an unconfigured
state (the neuron application
is not running).
Neuron Configuration
Neuron Configuration