Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485
Troubleshooting
5-7
Figure 5-4. TLS-IB Firmware Update Screen
8.
Select the Comm Port of the connected laptop using the up/down arrows of the
Comm Port
selector.
9.
Select the communication parameters,
Baud Rate
,
Parity
,
Data
and
Stop Bit
to connect to the TLS-IB
using the up/down arrows for each selection.
10. Use the
Security Code
checkbox when security code is enabled to connect to the TLS-IB.
11. Select the
Verify Setups
button to validate all the settings.
a. Verify that the firmware upgrade exists and valid.
b. Verify that the communications are setup correctly.
c. Verify that the TLS-IB Console is ready to accept firmware upgrade.
12. Click the
Run Upgrade
button to start the firmware upgrade. This button will be activated when setup has
been verified. As the firmware is being upgraded, status messages will be displayed in the Status Window.
13. Select the
Clear
button to clear status messages written in the Status Window.
14. Select the
Exit
button to exit the TLSIB_Upgrade program.
15. Turn Off AC power to the TLS-IB.
16. Disconnect the laptop serial cable from J3 on the CPU/Power Supply board.
17. Reconnect the site’s three serial comm wires back into the Serial Com plug, observing their previously marked
positions as you do so.
18. Switch On power to the TLS-IB and check your system configuration for proper setup.
Status Window
C:\Program Files (x86)\Veeder-Root\TLS-IB\349876-001A.txt
OFF
CC