Communication Setup - VaporTEK Interface
Setup with Laptop
42
16. Pulse – Ratio: Press ‘
7
’
This sub items allows a modification of Pulse Ratio. The pulse ratio defines the fuel flow rate which has to
match the dispenser flow rate. Refer to the dispenser manufacturer’s manual to input the correct pulse ratio.
17. Re-regulation factors: Press ‘
8
’
Use item 8 to review the re-regulation factors those will be controlled by the intelligent re-regulation of
monitoring. The permitted re-regulation range is (85 – 125)%. A factor value of 100 represents 100%.
New Connection Hyperterminal
File Edit View Call Transfer Help
Print echo
Capture
NUM
CAPS
SCROLL
9600-8-N-1
Auto detect
Connected 0:02:44
7. Pulse - Ratio
------------------
Pulse rate [Imp/l] = 100
Pulse Prescaler = 1
Pulse Prescaler x Pulse rate = 100 pulse/1
do you want to change these [Y/N]? Y
Input Pulse Ratio [pulse/l] (10 - 250):136
New Pulse Prescaler(1...10):1
Data have been written successfully
Pulse rate [Imp/l] = 136
Pulse Prescaler = 1
Pulse Prescaler x Pulse rate = 136 pulse/1
New Connection Hyperterminal
File Edit View Call Transfer Help
Print echo
Capture
NUM
CAPS
SCROLL
9600-8-N-1
Auto detect
Connected 0:02:44
8. Show Reregulation factors
----------------------------
side A = 100
side B = 100
do you want to change these [Y/N]? N