Calibration
LFXG-H Installation and Operation Guide
47
The linearizer curve maps on 2 axes so it indicates % Count Range vs. %
Span.
To construct the linearizer table, a data point calculates for every 2.5% of
the span. View or edit these points in the Linearizer table screen.
Simple calibration method
This method does not require collecting intermediate data points.
The internal software calculates a straight line between the Min Level and
Max Level based on the Cal Low Level and Cal High Level.
Choosing the linearizer type
The gauge’s response curve is non-linear, due to the measurement method
of radiation transmission. The linearizer determines the shape of the curve
between the endpoints.
The gauge’s linearizer type is part of the signal processing necessary to
produce a linear final output with respect to the change in level of process
material.
% Count Range
100%
Standard
Simple
100%
% Span
0%
0%
% Count range vs. % Span (in linearizer table)