2
1
F
ig
.
12
:
L
oosen the screws
1
E
lectronics module
2
S
crews
(
2
pcs
.)
6
R
emove the old oscillator
7
C
ompare the new oscillator with the old one
.
T
he type label
of the oscillator must correspond to that of the old
oscillator
.
T
his applies particularly to instruments used in
hazardous areas
.
8
C
ompare the settings of the two oscillators
.
S
et the
adjustment elements of the new oscillator to the settings of
the old oscillator
.
I
nformation
:
M
ake sure that the housing is not rotated during the electronics
exchange
.
O
therwise the plug may be in a di
ff
erent position
later
.
9
I
nsert the oscillator carefully
.
M
ake sure that the plug is in
the correct position
.
10
S
crew in and tighten the two screws with a
P
hillips
screwdriver
.
11
I
nsert the wire ends into the open terminals according to
the wiring plan
12
C
lose the opening levers of the terminals
,
you will hear the
terminal spring closing
13
C
heck the hold of the wires in the terminals by lightly
pulling on them
14
C
heck the tightness of the cable entry
.
T
he seal ring must
completely encircle the cable
.
15
S
crew the housing cover back on
24
VEGACAP
66
-
with relay output
M
aintenance and fault recti
fi
cation
30020
-
EN
-
050920