Mounting

* DG-hole on instrument

2 Mounting

2.1 Mounting instructions

VEGADIS 371Ex indicating instrument can be either
mounted directly to the wall with three screws, plugged
on carrier rail 35 x 7,5 acc. to DIN EN 50 022 or
lowered into a front panel. VEGADIS 371Ex must be
generally mounted outside hazardous areas.

Before mounting VEGADIS 371 you should adjust the
requested sensor signal (I

a

, I

p

, U). The slide switch on

the rear of VEGADIS 371 under the cover is no more
accessible after mounting the instrument.
Dependent on the application and the sensor you can
choose between active current measurement (I

a

),

passive current measurement (I

p

) or voltage

measurement (U). Factory setting "I

a

“ see also

"4.2 Adjustment“. The position of the switch also
modifies the application conditions for Ex-instruments
(VEGADIS 371Ex). Note the type approval or the
conformity certificate of VEGADIS 371Ex.

Carrier rail mounting

• Place the adapter plate (A) to the rear of VEGADIS

371 (spring of the adapter plate to the bottom) and
tighten the plate with screw B (M4 x 6).

• Place VEGADIS 371 from the bottom to the carrier

rail (C) and push the instrument to the top until
snap-in.

Wall mounting

• Insert the metal sleeve (D) from top into the housing

cut-out.

• Fasten the instrument with three screws (ø max.

4 mm) directly to the wall.

Front panel mounting

• Remove the two pluggable terminal boards (F) and

the terminal board (K) to the top.

• Screw the pin (H) to the rear of VEGADIS 371 and

tighten with a screwdriver.

• Insert VEGADIS 371 from the front into the front

panel (E).

• Push the terminal strap (G) from the back to the pin

(H) and pull with the knurled nut (I) against the front
panel (E).

Front panel
cut-out

Cover

;;

;

;

61

43,5

;

;

;

;

;

;;

;;

;;

;

;

;

;

;

A

B

C

105

80

Ø4,5*

D

Summary of Contents for VEGADIS 371 Ex

Page 1: ...8888 Operating Instruction VEGADIS 371 Ex VEGADIS 371 Ex 16 85 ...

Page 2: ...duct description 1 1 Function and configuration 3 1 2 Types and versions 3 1 4 Dimensions 3 1 3 Approvals 3 1 5 Technical data 4 2 Mounting 2 1 Mounting instructions 5 3 Electrical connection 3 1 Sensor connection 6 3 2 Sensor connection Ex area 7 3 3 Terminal coordination 8 3 4 Ex separating chamber 8 4 Set up 4 1 Indicating and adjustment elements 9 4 2 Adjustment 11 4 3 Mounting of the relay mo...

Page 3: ...rument with integral level switches for front panel mounting or surface mounting VEGADIS 371 Ex Digital indicating instrument with integral level switches for front panel mounting or surface mounting with Ex approval 1 3 Approvals VEGADIS 371 Ex appropriate apparatus is available with the following approval Explosion protection Classification II 1G EEx ia IIC EC type approval TÜV 97 ATEX 1174 Conf...

Page 4: ...mption 4 W 12 5 VA Sensor input floating Transmission analogue Connection line to the sensor 2 wire Iactive sensor supply 25 15 V range 4 20 mA shortcircuit limitation approx 30 mA Ipassive inner resistance 250 Ω range 4 20 mA U inner resistance 100 kΩ range 0 10 V Current output 0 4 20 mA signal circuit floating Resolution 0 1 range 0 4 20 mA max load 500 Ω Fault signal approx 22 mA Linearity err...

Page 5: ...e switch also modifies the application conditions for Ex instruments VEGADIS 371Ex Note the type approval or the conformity certificate of VEGADIS 371Ex Carrier rail mounting Place the adapter plate A to the rear of VEGADIS 371 spring of the adapter plate to the bottom and tighten the plate with screw B M4 x 6 Place VEGADIS 371 from the bottom to the carrier rail C and push the instrument to the t...

Page 6: ...the voltage supply before starting connection work Active operation Ia 1 Passive operation Ip 1 1 Active or passive operation selectable with slide switch See 4 1 Indicating and adjustment elements Sensor Signal conditioning instrument VEGAMET Sensor Voltage supply Voltage supply 4 20 mA output 4 20 mA ...

Page 7: ...enerally mounted outside hazardous areas Passive operation Ip 1 Electrical connection Intrinsically safe passive sensor e g pressure transmitter Signal and supply circuit sensor is powered 4 20 mA Ex area Ex area Active intrinsically safe signal circuit 4 20 mA VEGAPULS 81 E Ex 1 Active or passive operation selectable with slide switch See 4 1 Indicating and adjustment elements Voltage supply Volt...

Page 8: ...e terminals of the sensor input terminals 1 and 2 and loop the sensor line to the front out of the Ex separating chamber Push the Ex separating chamber to the front until snap in 3 3 Terminal coordination Relay 3 Rel 4 Relay 2 Relay 1 Relay module 2 Relay module 1 Voltage supply When switching on voltage supply the software version of VEGADIS 371 is displayed for approx 4 seconds Tipp For paramete...

Page 9: ...rewdriver by a quarter turn and the cover 5 opens To protect the instrument against unauthorized adjustment the cover 5 of VEGADIS 371 can be sealed Insert the seal wire with closed cover in the top left corner through the hole of the lug Designation In practise it has proven to mark VEGADIS Informati on on the appropriate measurement loop and the unit of the indicated value help to avoid failures...

Page 10: ...on conditions for Ex instruments VEGADIS 371 Ex Also note the type approval or the conformity certificate of VEGADIS 371 Ex Rotating switch 7 Stage 1 In menu stage 1 you find all necessary functions which are necessary for adjustment of the indicating instrument When you are in menu stage 1 the VEGA logo is shown non flashing Note When you want to activate the pump changeover function all relay ou...

Page 11: ...se Ia active current input Current output Set the rotating switch 7 to position A With the keys 3 and 4 you can choose between measured value output 4 20 mA or 0 20 mA For the given example choose 4 20 The display indications have the following meaning 0 20 0 20 mA 4 20 4 20 mA VEGADIS 371 requires for the scaling of the indication the adjustment of the volumes for 4 mA and 20 mA The vessel must n...

Page 12: ... condition and switched on when min level is reached Mode B dry run protection switch on point switch off point When you want to adjust mode B dry run protection for relay 1 you have to enter with position 1 relay 1 on of the rotating switch 7 the higher value and with position 2 relay 1 off the lower value Hence relay 1 is switched on when Set up max level is reached and switch off deenergized co...

Page 13: ...hen a certain level is reached The first pump should switch on at 80 filling When the level increases a second pump should be switched on at 90 Both pumps should be switched off again at 10 filling Enter the values of the concerned relays in stage 1 as follows 1 Relay 1 on 80 0 2 Relay 1 off 10 0 3 Relay 2 on 90 0 4 Relay 2 off 10 0 Set the rotating switch to position 0 Operate Change to the menu ...

Page 14: ...on of a relay is activated the working times can be enquired positions of the rotating switch 2 4 6 8 The working times of the relays which are coordinated to the pump changeover function are saved every 8 hours in the EEPROM i e the data saved last remain even in case of power failure The working time is indicated in hours The max indication is 9999 hours over 1 year If this value is exceeded the...

Page 15: ...d the two keys pushed Switch on the supply voltage The display indicates RES The instrument carries out a reset VEGADIS 371 has the following fatory setting Reset Default values Factory setting Menu stage 1 Relay switch on points 10 0 Relay switch off points 100 0 Display min 0 Display max 100 Decimal point 1 position Integration time 0 s Offset correction 0 μA Current output 4 20 mA Menu stage 2 ...

Page 16: ...ce all adjusted values are reset to factory setting When the failure occurs again send the instrument to our repair department E014 Shortcircuit Relays deenergize safe condition current output 22 mA Sensor current 21 mA Check the terminals and the connection line to the sensor E015 Line break Relays deenergize safe condition current output 22 mA Sensor current 3 6 mA Check the terminals and the co...

Page 17: ...VEGADIS 371 Ex 17 Notes ...

Page 18: ...18 VEGADIS 371 Ex Notes ...

Page 19: ...VEGADIS 371 Ex 19 Notes ...

Page 20: ...ions of the sensors and processing systems correspond to the actual knowledge at the date of printing Technical data subject to alteration VEGA Grieshaber KG Am Hohenstein 113 D 77761 Schiltach Phone 0 78 36 50 0 Fax 0 78 36 50 201 e mail info de vega com 19893 EN 060426 ...

Reviews: