I
n this menu item
,
the actual measured value is accepted as min
.
adjustment for the sensor
6
)
T
his is a zero adjustment to which
0
%
of the current output are
assigned
.
T
he value accepted hier
,
shifts the measuring range end
!
T
he di
ff
erence between measuring range begin and end however
remains
.
I
n this menu item
,
the integration time for damping the measured value
is entered
.
A
djustment range
:
0
.
0
…
999
s
A
djustment of the
HART
address of the assigned transmitter in
M
ultidrop mode
.
W
ith standard current loop operation
,
this address
must always be set to
0
.
A
djustment range
:
0
…
15
A
djustment of the unit for the digital indication
.
F
irst of all the unit
selected in the menu
"
M
easurement
"
,
for example m appears
.
F
urthermore the units from the same unit group such as e
.
g
.
mm
,
cm
,
m etc
.
are available
.
T
he measured values are automatically converted
into the selected unit
.
I
f
%
is selected as unit
,
then the
VEGADIS
62
converts the actual loop
current into a
%
value relating to the max
.
loop current
.
I
f m
A
is
selected as a unit
,
then the actual loop current is displayed in m
A
.
6
)
I
s not available with
HART
multidrop
.
M
easurement
/
L
ive ad
-
justment zero point
M
easurement
/
D
amping
M
easurement
/
A
ddress
I
ndication
/
U
nit
VEGADIS
62
27
6
S
et parameters
36469
-
EN
-
120329