VEGAMET 141, 142 • Installation in non-Ex area
63696-01-201218
•
The staff must be trained in explosion protection
•
The staff must be familiar with the respectively valid regulations, e.g. planning and installation
acc. to EN 60079-14
•
Make sure when working on the instrument (mounting, installation, maintenance) that there is no
explosive atmosphere present, the supply circuits should be voltage-free, if possible.
•
The instrument has to be mounted according to the manufacturer specifications, the EU type
approval certificate and the valid regulations and standards
•
Modifications on the instrument can influence the explosion protection and hence the safety,
therefore repairs are not permitted to be conducted by the end user
•
Modifications must only be carried out by employees authorized by VEGA company
•
Use only approved spare parts
•
Components for installation and connection not included in the approval documents are only
permitted if these correspond technically to the latest standard mentioned on the cover sheet.
They must be suitable for the application conditions and have a separate certificate. The special
conditions of the components must be noted and if necessary, the components must be inte-
grated in the type test. This applies also to the components already mentioned in the technical
description.
Mounting
Keep in mind for instrument mounting
•
Mechanical damage on the instrument must be avoided
•
Mechanical friction must be avoided
Maintenance
To ensure the functionality of the device, periodic visual inspection is recommended for:
•
Secure mounting
•
No mechanical damages or corrosion
•
Worn or otherwise damaged cables
•
No loose connections of the line connections, equipotential bonding connections
•
Correct and clearly marked cable connections
Intrinsic safety "i"
•
Observe the valid regulations for the interconnection of intrinsically safe circuits.
•
The instrument is only suitable for connection to certified, intrinsically safe instruments
•
If the intrinsically safe circuit is led into dust-explosive areas of zone 20 or 21, please make sure
that the instruments connected to these circuits meet the requirements of category 1D (EPL Da
instruments) or 2D (EPL Db instruments) and are certified respectively
8
Electrical data
VEGAMET 141, 142
Non-intrinsically safe circuit
Supply circuit:
Terminals 91[+, L], 92[-, N]
U = 24 … 65 V DC (-15 … +10 %)
P = 3 W (VEGAMET 141), 4 W (VEGAMET 142)
U = 100 … 230 V AC (-15 … +10 %), 50/60 Hz
P = 10 VA (VEGAMET 141), 12 VA (VEGAMET 142)
U
m
= 253 V AC
ATEX
Summary of Contents for VEGAMET 141
Page 32: ...30 Notes VEGAMET 141 142 Installation im Nicht Ex Bereich 63696 01 201218 ATEX ...
Page 33: ...31 Notes VEGAMET 141 142 Installation im Nicht Ex Bereich 63696 01 201218 ATEX ...
Page 52: ...10 Notes VEGAMET 141 142 63696 EN 210721 c UL us ...
Page 53: ...11 Notes VEGAMET 141 142 63696 EN 210721 c UL us ...