à
S
end instrument for repair
?
E
007
l
S
ensor type not compatible
à
S
earch for sensor again and allocate under
"
M
eas
.
loop
-
I
nput
"
?
E
008
l
S
ensor not found
à
C
heck connection of the sensor
à
C
heck
HART
address of the sensor
?
E
011
l
N
o
HART
sensor assigned
à
A
ssign a sensor in the menu
"
I
nput
"
?
E
013
l
S
ensor signals failure
,
no valid measured value
à
C
heck sensor parameter adjustment
à
S
end sensor for repair
?
E
016
l
E
mpty
/
full adjustment reversed
à
C
arry out a fresh adjustment
?
E
017
l
A
djustment span too small
à
C
arry out a fresh adjustment and increase the distance
between min
.
and max
.
adjustment
?
E
021
l
S
caling span too small
à
C
arry out a fresh scaling
,
increase the distance between min
.
and max
.
scaling
.
?
E
026
l
U
nits of the input variable are di
ff
erent
(
only di
ff
erential
measurement loop
)
à
A
dapt the units of both
à
U
se sensors with the same input variable
54
VEGAMET
625
•
D
ouble channel
HART
signal conditioning instrument
9
M
aintenance and fault recti
fi
cation
28970
-
EN
-
110801