background image

7

VEGAPULS 61

37991-EN-200303

Indicating and adjustment circuit: (termi

-

nals 5, 6, 7, 8 in electronics compartment 

or plug connection; with double chamber 

housing version in the connection com-

partment)

In type of protection intrinsic safety Ex ia IIC
For connection to the intrinsically safe circuit of the 

associated external indicating unit VEGADIS 61/81 

(PTB 02 ATEX 2136 X).
The rules for the interconnection of intrinsically safe 

circuits between VEGAPULS PS61(*).C****P/K/F/L**** 

and the external indicating unit VEGADIS 61/81 are 

fulfilled, provided that the total inductance and total ca

-

pacitance of the connection cable between VEGAPULS 

PS61(*).C****P/K/F/L**** and the external indicating unit 

VEGADIS 61/81 L

cable

 = 310 µH and C

cable

 = 2 µF are not 

exceeded.
When using the delivered VEGA connection cable 

between VEGAPULS PS61(*).C****P/K/F/L**** and the 

external indicating unit VEGADIS 61/81, the following 

listed cable inductances L

i

 and cable capacitances C

i

 

must be taken into account with a cable length ≥ 50 m.

• 

L

i

' = 0.62 µH/m

• 

C

i

'

wire/wire

 = 132 pF/m

• 

C

i

'

wire/screen

 = 208 pF/m

• 

C

i

'

screen/screen

 = 192 pF/m

Circuit of the display and adjustment 

module: (spring contacts in the electron

-

ics compartment; with double chamber 

housing version also in the connection 

compartment)

In type of protection intrinsic safety Ex ia IIC
Only for connection to the display and adjust-

ment module PLICSCOM or VEGACONNECT 

(PTB 07 ATEX 2013 X).

With the double chamber housing version, the display 

and adjustment module may be mounted either in the 

electronics compartment or in the termination compart-

ment.

For applications requiring instruments of category 2G, the intrinsically safe power supply and signal 

circuit can correspond to protection class ia or ib. For connection to a circuit with protection class ib, 

the ignition protection type identification is Ex ib IIC T6.
For applications requiring instruments of category 1G or 1/2G, the intrinsically safe power supply 

and signal circuit must correspond to protection class ia.

For applications requiring instruments of category 1G or 1/2G the VEGAPULS PS61(*).C****P/K/

F/L**** is preferably connected to appropriate equipment with galvanically isolated, intrinsically safe 

circuits.

The metal parts of the level measuring instruments on radar basis type VEGAPULS PS6* are electri

-

cally connected to the earth terminals.

In the versions of the radar sensors VEGAPULS PS61(*).C****P/K/F/L**** the intrinsically safe 

circuits are electrically isolated from elements that may be earthed.

Application conditions

The max. permissible ambient temperatures depending on the temperature classes are specified in 

the following tables.
For assessment and reduction of the explosion risk, valid standards such as for example EN 1127-1 

must be taken into account.

Summary of Contents for VEGAPULS 61 Series

Page 1: ...8 7 Use of an overvoltage arrester 9 8 Grounding 9 9 Impact and friction sparks 9 10 Material resistance 9 11 Mounting with external display unit VEGADIS 61 81 9 12 Removing and replacing the red thre...

Page 2: ...k ytt varten EL DE Die vorliegenden Sicherheitshinweise sind im Download unter www vega com standard m ig in den Sprachen deutsch englisch franz sisch und spanisch verf gbar Weitere EU Landessprachen...

Page 3: ...tible liquids gases mist or vapour The VEGAPULS PS61 C P K F L are suitable for use in hazardous atmospheres of all combustible materials of explosion group IIA IIB and IIC for applications requiring...

Page 4: ...s L Two wire Foundation Fieldbus with increased sensitivity g Housing Protection K Plastic single chamber IP66 IP67 A Aluminium single chamber IP66 IP68 0 2 bar H Special colour Aluminium single chamb...

Page 5: ...ns then these will be mentioned explic itly with their type code 4 Technical data Electrical data Type of protection intrinsic safety Ex i Power supply and signal circuit termi nals 1 2 in electronics...

Page 6: ...insic safety Ex ia IIC Only for connection to the display and adjust ment module PLICSCOM or VEGACONNECT PTB 07 ATEX 2013 X With the double chamber housing version the display and adjustment module ma...

Page 7: ...or also in case of failure does not generate heat itself Responsibility for safe operation of the equipment with respect to pressures temperatures of the materials used rests with the operator The pre...

Page 8: ...trostatically connected to the local potential equalisation transfer resistance 1 M e g via the ground terminal when used as category 1G or 1 2G instru ments Metallic adapter flanges must be earthed e...

Page 9: ...ice and the openings must be sealed according to the requirements of the type of protection and the IP protection type specified on the type label When using certified i e suitable cable glands sealin...