9 Diagnosis, asset management and service
VEGAPULS 65 • Foundation Fieldbus
36518-EN-140209
Code
Text mes-
sage
Cause
Rectification
PA DevS-
pec
Diagnosis
F125
Imper
-
missible
electronics
tempera
-
ture
–
Temperature of the
electronics in the non-
specified section
–
Check ambient tem
-
perature
–
Isolate electronics
–
Use instrument with
higher temperature
range
Bit 8
F260
Error in the
calibration
–
Error in the calibra
-
tion carried out in the
factory
–
Error in the EEPROM
–
Exchanging the elec
-
tronics
–
Send instrument for
repair
Bit 9
F261
Error in the
configura
-
tion
–
Error during setup
–
False signal suppres
-
sion faulty
–
Error when carrying
out a reset
–
Repeat setup
–
Repeat reset
Bit 10
F264
Installa
-
tion/Setup
error
–
Adjustment not within
the vessel height/
measuring range
–
Max. measuring range
of the instrument not
sufficient
–
Check or correct
installation and/or
parameter adjustment
–
Use an instrument
with bigger measuring
range
Bit 11
F265
Meas
-
urement
function
disturbed
–
Sensor no longer
carries out a measure
-
ment
–
Operating voltage
too low
–
Check operating
voltage
–
Carry out a reset
–
Disconnect operating
voltage briefly
Bit 12
The following table shows the error codes and text messages in the
status message "
Function check
" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause
Rectification
C700
Simulation ac
-
tive
–
A simulation is active
–
Finish simulation
–
Wait for the automatic end
after 60
mins.
The following table shows the error codes and text messages in the
status message "
Out of specification
" and provides information on
causes as well as corrective measures.
Function check
Out of specification