6 Set up with the display and adjustment module PLICSCOM
VEGAPULS 66 • 4 … 20 mA/HART - two-wire
28438-EN-170927
Menu item
Reset value
Medium
Liquid
Vessel form
not known
Damping
0 s
Linearisation
Linear
Sensor-TAG
Sensor
Displayed value
Distance
Extended settings
None
Current output - characteristics
4 … 20 mA
Current output - max. current
20 mA
Current output - min. current
4 mA
Current output - failure
< 3.6 mA
Unit of measurement
m(d)
The values of the following menu items are
not
reset to the reset
values (see table) with "
Reset
":
Menu item
Reset value
Backlight
No reset
Language
No reset
SIL
No reset
HART mode
No reset
Default setting
Like basic adjustment, but in addition, special parameters are reset to
default values.
7)
Peak value indicator
The min. and max. distance values are reset to the actual value.
In this menu item you select the internal arithmetic unit of the sensor.
Unit of measurement
m(d)
The sensor is already set to the ordered national language. In this
menu item you can change the language. The following languages are
available, e.g. in software version 3.50:
•
Deutsch
•
English
•
Français
•
Espanõl
•
Pycckuu
Service - Adjustment unit
Service - Language
7)
Special parameters are parameters which are set customer-specifically on
the service level with the adjustment software PACTware.