11
5 Connecting to power supply
VEGATOR 121 •
57662-EN-210714
5.2 Connection procedure
The pluggable terminals can be removed as needed to allow more
convenient connection. To make the electrical connection, proceed as
follows:
1. Mount the instrument as described in the previous chapter
2. Connect sensor cable to terminal 1/2, and where applicable, con-
nect the shielding
3. Connect switched-off power supply to terminal 16/17
4. Connect relay to terminal 10/11/12
5. Option with fail safe relay: Connect relay to terminal 13/14/15
The electrical connection is finished.
5.3 Wiring plan
1
2
4
3
13 1415
10 1112
-
+
1 2
-
+
1617
OPEN
1 Sensor circuit (8/16 mA)
2 Relay output
3 Fail safe relay/second relay output (optional)
4 Voltage supply