1
S
et
DIL
switch
1
to
3
on the
DIL
switch block
(
A
)
according to the
following illustration
1 KΩ
10 KΩ
200 KΩ
10 KΩ
CH1
CH2
max.
max.
off on
1
2
3
4
5
6
7
F
ig
.
126
:
R
esistance range up to
10
k
Ω
2
T
urn potentiometer
(
B
)
to complete left position
3
T
urn potentiometer
(
B
)
slowly clockwise until the relay output
switches and the yellow control lamp changes condition
4
T
urn the potentiometer approximately
15
°
in the same direction
5
I
f the relay output does not change
,
you have to switch to the next
range
.
I
f the relay output has switched
,
empty the vessel until the electrode is
uncovered
.
T
he relay output must now switch again
.
A
djustment in liquids with resistance range up to
1
k
Ω.
S
peci
fi
cations
:
T
he probe is covered with medium
.
1
S
et
DIL
switch
1
to
3
on the
DIL
switch block
(
A
)
according to the
following illustration
1 KΩ
10 KΩ
200 KΩ
1 KΩ
CH1
CH2
max.
max.
off on
1
2
3
4
5
6
7
F
ig
.
127
:
R
esistance range up to
1
k
Ω
2
T
urn potentiometer
(
B
)
to complete left position
R
esistance range up to
1
k
Ω
38
VEGATOR
632
•
S
ignal conditioning instrument
9
S
et up
-
T
wo
-
channel control
35243
-
EN
-
120228